12.2.4.1 - Physical properties of units with partial heat recovery using desuperheaters
AQUACIAT
POWER™
LD
0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Desuperheater in circuits A/B
Brazed-plate heat exchanger
Water volume circuits A/B
l
2 /
3.75
2 /
3.75
3.75 /
3.75
3.75 /
3.75
3.75 /
3.75
3.75 /
5.5
3.75 /
5.5
5.5 /
5.5
5.5 /
5.5
5.5 /
7.5
Maximum operating pressure, water side
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic connections
Victaulic
Connection
in
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
External diameter
mm
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
Operating weight
(1)
Standard unit + desuperheater option
kg
1409
1457
1457
1581
1616
2055
2109
2271
2329
2757
Unit + Ultra Low Noise + desuperheater option
kg
1492
1540
1540
1690
1725
2182
2236
2416
2474
2920
Unit + Ultra Low Noise + HP dual-pump hydraulic
desuperheater option
kg
1627
1675
1675
1825
1871
2331
2431
2611
2669
3154
Unit + Ultra Low Noise + HP dual-pump hydraulic
Water buffer tank desuperheater option
kg
2610
2658
2658
2808
2854
3318
3417
3597
3654
4146
AQUACIAT
POWER™
LD
1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
Desuperheater in circuits A/B
Brazed-plate heat exchanger
Water volume circuits A/B
l
5.5 /
7.5
7.5 /
7.5
7.5 / 11 11 / 11 11 / 11 11 / 15 11 / 15 15 / 15 15 / 15
Maximum operating pressure, water side
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic connections
Victaulic
Connection
in
2"
2"
2"
2"
2"
2"
2"
2"
2"
External diameter
mm
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
Operating weight
(1)
Standard unit + desuperheater option
kg
2782
2987
3325
3571
3571
4102
4102
4351
4351
Unit + Ultra Low Noise + desuperheater option
kg
2945
3168
3458
3724
3724
4276
4276
4545
4545
Unit + Ultra Low Noise + HP dual-pump hydraulic
desuperheater option
kg
3179
3439
3768
4034
4034
4665
4665
4934
4934
Unit + Ultra Low Noise + HP dual-pump hydraulic
Water buffer tank desuperheater option
kg
4171
4431
4775
5041
5041
5686
5686
5955
5955
(1) Weights are guidelines only. Refer to the unit name plate.
AQUACIAT
POWER™
ILD
0602R
0700R
0800R
0900R
1000R
1150R
Desuperheater in circuits A/B
Brazed-plate heat exchanger
Water volume circuits A/B
l
2 / 3.75
2 / 3.75
3.75 / 3.75 3.75 / 3.75 3.75 / 3.75 3.75 / 5.5
Maximum operating pressure, water side
kPa
1000
1000
1000
1000
1000
1000
Hydraulic connections
Victaulic
Connection
in
2"
2"
2"
2"
2"
2"
External diameter
mm
60,3
60,3
60,3
60,3
60,3
60,3
Operating weight
(1)
Standard unit + desuperheater option
kg
1651
1657
1873
1900
1906
2500
Unit + Ultra Low Noise + desuperheater option
kg
1735
1741
1981
2009
2015
2626
Unit + Ultra Low Noise + HP dual-pump hydraulic
desuperheater option
kg
1870
1876
2128
2156
2162
2821
Unit + Ultra Low Noise + HP dual-pump hydraulic
Water buffer tank desuperheater option
kg
2853
2859
3111
3138
3144
3831
AQUACIAT
POWER™
ILD
1250R
1400R
1500R
1600R
1750R
2000R
Desuperheater in circuits A/B
Brazed-plate heat exchanger
Water volume circuits A/B
l
3.75 / 5.5
3.75 / 7.5
3.75 / 7.5
5.5 / 7.5
5.5 / 7.5
7.5 / 7.5
Maximum operating pressure, water side
kPa
1000
1000
1000
1000
1000
1000
Hydraulic connections
Victaulic
Connection
in
2"
2"
2"
2"
2"
2"
External diameter
mm
60,3
60,3
60,3
60,3
60,3
60,3
Operating weight
(1)
Standard unit + desuperheater option
kg
2558
2785
2791
3283
3309
3565
Unit + Ultra Low Noise + desuperheater option
kg
2685
2930
2936
3446
3472
3746
Unit + Ultra Low Noise + HP dual-pump hydraulic
desuperheater option
kg
2880
3164
3170
3681
3744
4018
Unit + Ultra Low Noise + HP dual-pump hydraulic
Water buffer tank desuperheater option
kg
3889
4173
4179
4680
4743
5017
(1) Weights are guidelines only. Refer to the unit name plate.
12 - OPTIONS
EN-57
AQUACIAT
POWER
™ LD/ILD
Summary of Contents for AQUACIAT POWER LD 1100R
Page 1: ...AQUACIAT POWER LD 602R 3500R ILD 602R 2000R 12 2021 10590 Instruction manual...
Page 81: ...EN 81 AQUACIATPOWER LD ILD...
Page 82: ......
Page 83: ......