AQUACIAT
POWER™
LD
0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Minimum system water volume, air
conditioning application
(litres)
431
468
516
568
676
777
864
949
1039
1126
Minimum system water volume,
industrial process application
(litres)
1121
1217
1342
1476
1758
2021
2247
2467
2702
2928
Water type heat exchanger flow rate
without hydraulic module Min
(1)
/Max
(2)
(l/s)
3.1 /
17.5
3.1 /
17.5
3.7 /
17.5
3.1 /
17.5
3.8 /
21.8
3.5 /
29.8
4.6 /
35.2
4.3 /
33.8
5.4 /
38.9
5.8 /
40.4
Water type heat exchanger flow rate
with low-pressure hydraulic module
Single min
(3)
/
Max (l/s)
3.1 / 12 3.1 / 12 3.7 / 12 3.1 / 12 3.8 / 15 3.5 / 19 4.6 / 20 4.3 / 20 5.4 / 28 5.8 / 29
Dual min
(3)
/
Max (l/s)
3.1 / 11 3.1 / 11 3.7 / 12 3.1 / 12 3.8 / 15 3.5 / 19 4.6 / 20 4.3 / 20 5.4 / 23 5.8 / 28
Water type heat exchanger flow rate
with high-pressure hydraulic module
Single min
(3)
/
Max (l/s)
3.1 / 14 3.1 / 14 3.7 / 14 3.1 / 14 3.8 / 16 3.5 / 18 4.6 / 25 4.3 / 25 5.4 / 25 5.8 / 29
Dual min
(3)
/
Max (l/s)
3.1 / 14 3.1 / 14 3.7 / 14 3.1 / 14 3.8 / 17 3.5 / 19 4.6 / 24 4.3 / 24 5.4 / 25 5.8 / 28
AQUACIAT
POWER™
LD
1800R
2000R
2200R
2400R
2650R
2800R
2950R
3200R
3500R
Minimum system water volume,
air conditioning application
(litres)
1209
1381
1542
1694
1816
1955
2017
2204
2359
Minimum system water volume,
industrial process application
(litres)
3144
3590
4009
4405
4723
5083
5245
5730
6132
Water type heat exchanger flow rate
without hydraulic module Min
(1)
/Max
(2)
(l/s)
6.2 /
41.6
6.9 /
43.4
7.3 /
57.3
7.3 /
57.3
7.3 /
57.3
8.3 /
62.7
8.3 /
62.7
8.3 /
62.7
8.3 /
62.7
Water type heat exchanger flow rate
with low-pressure hydraulic module
Single min
(3)
/
Max (l/s)
6.2 / 29 6.9 / 27
-
-
-
-
-
-
-
Dual min
(3)
/
Max (l/s)
6.2 / 29 6.9 / 27
-
-
-
-
-
-
-
Water type heat exchanger flow rate
with high-pressure hydraulic module
Single min
(3)
/
Max (l/s)
6.2 / 29 6.9 / 29
-
-
-
-
-
-
-
Dual min
(3)
/
Max (l/s)
6.2 / 28 6.9 / 34
7.3 /
42.4
7.3 /
42.4
7.3 /
42.4
8.3 /
50.4
8.3 /50.4
8.3 /
50.4
8.3 /
50.4
AQUACIAT
POWER™
ILD
0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R
Minimum system water volume,
air conditioning application - cooling
(litres)
388
425
488
550
588
700
763
863
900
975
1050 1213
Minimum system water volume, air
conditioning application - heating
(litres)
1360 1520 1840 2000 2080 2480 2640 2960 3120 3400 3600 4160
Minimum system water volume,
industrial process application
(litres)
1008 1105 1268 1430 1528 1820 1983 2243 2340 2535 2730 3153
Water type heat exchanger flow rate
without hydraulic module Min
(1)
/Max
(2)
(l/s)
3.1 /
17.5
3.7 /
17.5
3.1 /
17.5
3.8 /
21.8
3.8 /
21.8
4.6 /
35.2
5.8 /
40.4
5.8 /
40.4
5.8 /
40.4
5.8 /
40.4
6.2 /
41.6
6.9 /
43.4
Water type heat exchanger flow rate
with low-pressure hydraulic module
Single min
(3)
/
Max (l/s)
3.1 /
12.0
3.7 /
12.0
3.1 /
13.6
3.8 /
14.7
3.8 /
14.7
4.6 /
20.1
5.8 /
28.8
5.8 /
28.8
5.8 /
28.9
5.8 /
28.10
6.2 /
29.7
6.9 /
30.1
Dual min
(3)
/
Max (l/s)
3.1 /
10.5
3.7 /
13.2
3.1 /
13.9
3.8 /
14.7
3.8 /
14.7
4.6 /
20.0
5.8 /
27.8
5.8 /
27.8
5.8 /
27.8
5.8 /
27.8
6.2 /
26.8
6.9 /
29.3
Water type heat exchanger flow rate
with high-pressure hydraulic module
Single min
(3)
/
Max (l/s)
3.1 /
14.1
3.7 /
14.1
3.1 /
15.2
3.8 /
16.0
3.8 /
16.0
4.6 /
25.0
5.8 /
25.5
5.8 /
25.6
5.8 /
25.7
5.8 /
28.5
6.2 /
28.6
6.9 /
34.9
Dual min
(3)
/
Max (l/s)
3.1 /
13.7
3.7 /
13.7
3.1 /
15.6
3.8 /
16.6
3.8 /
16.6
4.6 /
24.4
5.8 /
25.0
5.8 /
28.2
5.8 /
28.2
5.8 /
28.2
6.2 /
33.3
6.9 /
33.7
(1) Minimum flow rate for maximum allowable water temperature difference conditions (10°K)
(2) Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger
(3) Minimum factory flow rate setting according to the type of pump
NOTE: For the Water Buffer Tank Module option, the volume of the tank must be taken into account: 550 litres
7.6 - Maximum system water volume
Units with a hydraulic module may include an expansion vessel
which limits the volume in the water loop.
The table below gives the maximum loop volume compatible with
the expansion vessel (for pure water or ethylene glycol depending
on the system's various concentrations and static pressures).
If this volume is less than the volume of the installed loop, then it
is necessary to add an extra expansion vessel within the system.
Product
602R - 1100R
1150R - 3500R
Static pressure
bar
1
2
2,5
1
2
2,5
Pure water
l
2400 1600 1200 3960 2640 1980
10% EG
l
1800 1200 900 2940 1960 1470
20% EG
l
1320 880 660 2100 1400 1050
30% EG
l
1080 720 540 1740 1160 870
40% EG
l
900 600 450 1500 1000 750
EG: