5.5 - Short circuit withstand current
Short-circuit withstand current (TN system
(1)
)
AQUACIAT
POWER™
LD
0602R
0650R
0750R
0900R
1100R
1200R
1350R
1400R
1600R
1750R
Rated short-circuit withstand
currents
Rated short time (1s) current - Icw
kA eff
8,5
8,5
8,5
8,5
8,5
20
20
20
20
20
Rated peak current - Ipk
kA pk
330
330
330
330
330
330
330
330
330
330
Value with upstream electrical
protection
(1)
Rated conditional short circuit
current Icc
kA eff
50
50
50
50
50
50
50
50
50
50
Associated protection - type
INS250
INS250
INS250
INS250
INS250
INS400
INS400
INS400
INS400
INS400
Associated protection - rating/reference
TM160D /
LV430840
TM200D /
LV431831
TM200D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
AQUACIAT
POWER™
LD
1800R
2000R
2200R
2400R
2650R
2800R
2950R
3200R
3500R
Rated short-circuit withstand currents
Rated short time (1s) current - Icw
kA eff
20
20
20
20
20
35
35
35
35
Rated peak current - Ipk
kA pk
330
330
330
330
330
330
330
330
330
Value with upstream electrical protection
(1)
Rated conditional short circuit current Icc
kA eff
50
50
50
50
50
50
50
50
50
Associated protection - type
INS500
INS500
INS630
INS630
INS630
INS800
INS800
INS800
INS800
Associated protection - rating/reference
Micrologic
2.3 630 A/
LV432893
Micrologic
2.3 630 A/
LV432893
Micrologic
2.3 630 A/
LV432893
Micrologic
2.3 630 A/
LV432893
Micrologic
2.3 630 A/
LV432893
Micrologic
5.0 800 A
/34426
Micrologic
5.0 800 A
/34426
Micrologic
5.0 800 A
/34426
Micrologic
5.0 800 A
/34426
AQUACIAT
POWER™
ILD
165R
180R
210R
230R
270R
310R
Rated short-circuit withstand currents
Rated short time (1s) current - Icw
kA eff
8,5
8,5
8,5
8,5
8,5
20
Rated peak current - Ipk
kA pk
330
330
330
330
330
330
Value with upstream electrical protection
(1)
Rated conditional short circuit current Icc
kA eff
50
50
50
50
50
50
Associated protection - type
INS250
INS250
INS250
INS250
INS250
INS400
Associated protection - rating/reference
TM160D /
LV430840
TM200D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
Micrologic
2.3 400 A/
LV432693
AQUACIAT
POWER™
ILD
330R
370R
400R
430R
470R
520R
Rated short-circuit withstand currents
Rated short time (1s) current - Icw
kA eff
20
20
20
20
20
20
Rated peak current - Ipk
kA pk
330
330
330
330
330
330
Value with upstream electrical protection
(1)
Rated conditional short circuit current Icc
kA eff
50
50
50
50
50
50
Associated protection - type
INS400
INS400
INS400
INS400
INS500
INS500
Associated protection - rating/reference
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 400 A/
LV432693
Micrologic
2.3 630 A/
LV432893
Micrologic
2.3 630 A/
LV432893
(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the recommended
protection.
Note: The short-circuit withstand current capability values above have been established for the TN system.
IT system: The short circuit holding current values given above for the TN system are not valid for IT; modifications are
required.