12 - OPTIONS
If required by a specific installation, the unit's maximum fan speed
can be configured in the Service Configuration menu. Refer to
the control manual.
The maximum configured speed applies to both the cooling and
heating modes.
The performances (capacity, efficiency, noise level) depend on
the fan speed and the ductwork. Please refer to the manufacturer's
electronic catalogue to evaluate the estimated impact on the
unit's operating conditions.
12.2.8.1 -
Specific installation on ductable units
IMPORTANT: In units which are ductable in heating mode,
dehumidification of ambient air, as well as defrosting the air
exchangers, produces a large volume of condensates which
must be dealt with on the unit installation site.
Ductable units must be installed on a waterproof base enabling
efficient drainage and evacuation of the condensate from the
heat exchangers.
Similarly, in case of low outdoor temperatures when air-cooled
exchangers freeze, the water from defrosting must be collected
so as to prevent any risk of flooding the rooms where the heat
pumps are installed.
The rotation speed of all the fans in the same circuit is controlled
in the same way. Therefore each circuit operates independently.
Each refrigerant circuit must have an independent ductwork
system so as to prevent any air recycling between the air-cooled
exchangers of different refrigerant circuits.
On ductable units, each fan is equipped with a factory-fitted
connection interface frame providing a link between the ductwork
itself.
12.2.8.2 -
Nominal and maximum air flow rate per
circuit and per unit type
ILD HE
Circuit A
Nominal/maximum
air flow rate (l/s)
Circuit B
Nominal/maximum
air flow rate (l/s)
602
4767 / 5720
9534 / 11441
650-900
9534 / 11441
9534 / 11441
902-1000
9534 / 11441
14301 / 17161
1150-1200
9534 / 11441
19068 / 22882
1400
14301 / 17161
19068 / 22882
1600-2000
19068 / 22882
19068 / 22882
12.2.8.3 - Air connection on discharge
Refer to the dimensional plans of the units for the precise dimensions of the connection interface. A flexible sleeve providing
connection to the ductwork is delivered with the unit.
Factory-installed duct connection interface on each fan
V-shaped air heat exchanger
Top view
View from side
Internal dimension of the
flexible sleeve connection frame
955x955x105mm
AQUACIAT
POWER
ILD
EN-62