background image

12

11

C

heck if the height difference between indoor unit & outdoor unit and the total length of refrigerant pipe meet 

system requirement.

R

efrigerant piping work follows the indoor unit and outdoor unit installation, connect the pipe at the indoor side 

first, then the outdoor side.

A

lways keep ends of tubing sealed by placing a cap or covering with tape during installation and do NOT 

remove them until you are ready to connect the piping.

B

e sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may 

cause condensation or burns if touched.
When the outdoor unit is the top position and the difference of level is over 10m, it is recommended that set
a oil return bend every 5~8m in the gas pipe. The radius of oil reture bend should be over than 10cm.

CAUTION

4.1 FLARING 

In case of needing brazing, work with Nitrogen gas blowing.
Improper torque will cause flare damage or gas leaks. 

CAUTION

Use separate thermal insulation pipes for gas & 
liquid pipes.
The thickness above is a standard of the indoor 
temperature  of  27°C and humidity of 80%. If install-
ing in an unfavorable conditions such as near bath-
rooms, kitchens, and other similar locations, 
reinforce the insulation.
Insulation’s heat-resistance temperature should 
be more than 120°C.
Use the adhesives on the connection part of insula-
tion to prevent moisture from entering. 
Repair and cover any possible cracks in the insula-
tion, specially check the bent part or hanger of 
pipe.

4.2 PIPING WORK

4.2.1 Align the center to tighten the flare nut and finish
         connection using two wrenches.

Flare nut

Wrench

Torque wrench

4.2.2 Select the appropriate insulation material for 
refrigerant pipe.(Min. 10mm, thermal insulating foam C)

Torque

Tubing size

18 ~ 20 N.m 

25 ~ 26 N.m 

35 ~ 36 N.m 

45 ~ 47 N.m 

65 ~ 67 N.m 

Φ6.35mm

Φ9.52mm

Φ12.7mm

Φ15.88mm

Φ19.05mm

After the piping work is finished, make sure to check the connection part of each refrigerant pipe and confirm 
that there is no gas leak by applying soapy water to them or by using a leak detector specific for HFC refrigerants. 
Refer below picture for illustration.

            A: Low pressure stop valve            B: High pressure stop valve
            C & D: Indoor unit flare nuts

Check-point of indoor unit

Check-point of outdoor unit

A

B

C

D

4.3 REFRIGERANT PIPE

NOTE
    The refrigerant should be charged from the service port on the outdoor unit’s low pressure valve.
    Extended pipe length will affect the capacity and energy efficiency of the unit.
    The nominal efficiency is tested based on the pipe length of 5 meter.     
    When the pipe length is over 5m, the additional refrigerant should be added according to the pipe length.
    The max. pipe length is recommended as below.

4.4 AIR EVACUATION

Connect the charge hose from the manifold gauge to the service port of the gas side packed valve.
Connect the charge hose to the port of the vacuum pump.
Fully open the handle Lo of manifold gauge.
Operate the vacuum pump to evacuate air from the system until -76cmHg.
Close the handle Lo of manifold gauge.
Fully open the valve stem of the packed valves.
Remove the charging hose form the service port.
Securely tighten caps of packed valve.

-76 cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Packed valve

Manifold valve

Compound gauge

Pressure meter

4.5 LEAKAGE TEST

Liquid side:

φ

9.52mm       

R410A

Chargeless length 

Additional charge per meter

Liquid side:

φ

6.35mm       

15g

30g

Minimum length 

to reduce abnormal 

vibration & noise 

3m

R32

5m

12g

24g

4. REFRIGERANT PIPING WORK

4. REFRIGERANT PIPING WORK

Max. height difference(m)

Inverter Model 

Capacity(kW)

25

Max. pipe length(m)     

10

30

20

40

20

18k

24k

NOTE
  Tools required for flaring are pipe cutter, reamer, 
flaring tool and pipe holder.
   For R32 refrigerant models, the pipe connection 
points must be placed outside of room.

90

Oblique                  Rough                   Burr

R0.4~0.8

45 °

±2

90 °     

± 4

A

4.1.1 Using a pipe cutter to cut the pipe to the 
         requested length. Ensure that the cut edge 

         remains at 90° with the side of the pipe. 

4.1.2 Use a reamer to remove burrs with the cut 
        surface downward so that the chips do not 
        enter the pipe.

4.1.3 Carry out flaring work using flaring tools as 
         below.

4.1.4 Check if the flaring is properly made. See 
         incorrectly flared pipes sample below.

Inclined         Damaged Surface          Cracked          Uneven Thickness

Outside diameter

A(mm)

Max

8.7

Φ6.35mm

Φ9.52mm

Φ12.7mm

Φ15.88mm

Φ19.05mm

12.4

15.8

19.0

23.3

8.3

12.0

15.4

18.6

22.9

Min

Refrigerant

* Please use tools for R410A/R32 system respectively.

* Please use tools for R410A/R32 system respectively.

GB

7k/9k/12k

Summary of Contents for 38HV09JS8C

Page 1: ...5 620 114 Document non contractuel Dans le souci constant d am liorer son mat riel CIAT se r serve le droit de proc der sans pr avis toutes modifications techniques Non contractual document With the t...

Page 2: ...imination 1 Votre municipalit a mis en place des syst mes de collecte gr ce auxquels les utilisateurs peuvent se d barrasser de leurs d chets lectroniques gratuitement 2 Lorsque vous achetez un nouvea...

Page 3: ...tion Ne modifiez pas cet appareil en retirant une protection ou en contournant les dispositifs de verrouillage de s curit Il convient que les travaux lectriques soient effectu s en conformit avec le m...

Page 4: ......

Page 5: ...3 Percer le trou dans le mur tape 8 Suspension de l unit int rieure Raccordement des c bles int rieurs 1 Soulevez le panneau avant de l appareil int rieur 2 Ouvrez le couvercle des composants lectriqu...

Page 6: ...t te du boulon de fixation mesure plus de 12mm Dimensions de l appareil ext rieur mm Dimensions de montage mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376...

Page 7: ...e cuisine et d autres endroits similaires renforcez l isolation Il convient que la temp rature de r sistance la chaleur de l isolation soit sup rieure 120 C Utilisez des adh sifs sur la partie de racc...

Page 8: ...es uniquement REMARQUE 1 Tous les fils lectriques doivent tre d une dimension conforme au code de c blage lectrique local r gional et national Consultez les codes de construction locaux et le code nat...

Page 9: ...iode o les travaux sont r alis s Il convient que la ventilation permette de dissiper le produit frigorig ne lib r en toute s curit et de pr f rence de le rel cher l ext rieur dans l atmosph re 7 8 V R...

Page 10: ...ATIVES L ENTRETIEN la taille de la charge est adapt e la taille de la pi ce dans laquelle les parties contenant le produit frigorig ne sont install es les appareils de ventilation et les orifices fonc...

Page 11: ...ment pouvant tre stock s ensemble sera d termin par les r glementations locales 7 INFORMATIONS RELATIVES L ENTRETIEN 7 16 PROC DURES DE CHARGEMENT Outre les proc dures conventionnelles de chargement l...

Page 12: ...k shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to access and service this product 5 Any handling of the fluorinated gas in this product such as when...

Page 13: ...from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use the specified cables for electrical connectio...

Page 14: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Page 15: ...ening the screws 3 Pass the connecting wires from the back of indoor unit and connect to the indoor terminal block Front panel The drain line must not have a trap anywhere in its length must pitch dow...

Page 16: ...tdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet The moun...

Page 17: ...ve C D Indoor unit flare nuts Check point of indoor unit Check point of outdoor unit A B C D 4 3 REFRIGERANT PIPE NOTE The refrigerant should be charged from the service port on the outdoor unit s low...

Page 18: ...earth connection for functional purposes only CAUTION 60mm 40mm 10mm Power input cord GND 60mm 40mm 10mm GND Connective Cable W 1 2 S L N Power Input To Indoor W 1 2 S L N Power Input To Indoor W 1 2...

Page 19: ...shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and...

Page 20: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Page 21: ...e labels on the equipment stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommend...

Page 22: ...cos Para su eliminaci n hay varias posibilidades 1 El municipio ha establecido sistemas de recogida en los que se pueden desechar los residuos electr nicos de forma gratuita para el usuario 2 En la co...

Page 23: ...la eliminaci n de cualquiera de las protecciones de seguridad ni se salte ninguno de los interruptores de seguridad El trabajo el ctrico debe llevarse a cabo de acuerdo con el manual de instalaci n y...

Page 24: ......

Page 25: ...Conexi n de cables de la unidad interior 1 Levante el panel frontal de la unidad interior 2 Abra la cubierta de los cables el ctricos de la unidad interior con un destornillador quite la cubierta de...

Page 26: ...nillo de fijaci n debe ser mayor de 12mm Dimensiones unidad exterior mm Dimensiones de montaje mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376 3 2 REQUISIT...

Page 27: ...o usando las herramientas de abocardado tal como se indica a continuaci n Di metro exterior A mm M x M n 6 35 mm 8 7 8 3 9 52 mm 12 4 12 0 12 7 mm 15 8 15 4 15 88 mm 19 0 18 6 19 05 mm 23 3 22 9 4 1 4...

Page 28: ...to incorpora una conexi n de toma de tierra solo para fines funcionales AVISO 1 Todos los cables de alimentaci n deben dimensionarse de acuerdo con el c digo de cableado el ctrico nacional Consulte la...

Page 29: ...a ventilaci n debe dispersar de forma segura todo el refrigerante liberado y expulsarlo preferiblemente a la atm sfera externa 7 8 COMPROBACIONES EN EL EQUIPO DE REFRIGERACI N Cuando se cambien compon...

Page 30: ...o de la sala en la que est n instalados los componentes que contienen refrigerante la maquinaria de ventilaci n y las salidas funcionan adecuadamente y no est n obstruidas si se utiliza un circuito d...

Page 31: ...voque una fuga de la carga de refrigerante El n mero m ximo de equipos que se permiten almacenar juntos estar determinado por las regulaciones locales 7 INFORMACI N PARA EL SERVICIO T CNICO 7 16 PROCE...

Reviews: