background image

08

07

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system ressures, 
electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and serve this equipment.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached 
to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher
nearby when brazing. Use care in handing, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the
unit. Consult local building codes and National Electrical Code for special requirement.

Note:
   The installation plate is fixed with a screw 
for the convenience of shipment, please 
remove the screw first before installation. 
(see figure)

  The mounting plate will look like one of 
the figure depending on the unit size.
The holes for fixing anchors should be 
5mm.

Screw

Right rear side
refrigerant pipe 

hole φ90

Left rear side 
refrigerant

pipe hole φ90

Indoor unit 
outline

(A: 1082, B:338)

A

B

219

581

300

53.5

53.5

76

174.3

44.7

15.3

47

151

148.7

(A: 973, B:319)

581

53.5

76

172

242

53.5

98

144

34

138

59

29

Right rear side
refrigerant pipe 

hole φ65

Left rear side 
refrigerant

pipe hole φ65

Indoor unit 
outline

A

B

(A: 812, B:300)

Right rear side
refrigerant pipe 

hole φ65

Left rear side 
refrigerant

pipe hole φ65

Indoor unit 
outline

A

B

228

243

43

6.6

6.6

46

43

175

135

(A: 730, B:291)

Right rear side
refrigerant pipe 

hole φ65

Left rear side 
refrigerant

pipe hole φ65

Indoor unit 
outline

A

B

209

184

14

38.5

51

101

136

Unit: mm

Unit: mm

Unit: mm

Unit: mm

Step 1: Determine Wall Hole Position 

Step 2: Attach Mounting Plate

Step 3: Drill Wall Hole

Fix the mounting plate horizontally and 
level on the wall with five or more A-type 
screws.

Install The Mounting Plate

Drill Hole In The Wall 

Indoor

Wall

Outdoor

5-7mm

Step 4: Connect Pipe

1

2

S

Step 5: Connect Wire

Step 6: Prepare Drain Hose

STEP 

8

     

Indoor Wire Connection

1. Lift the indoor unit front panel.
2. Open the indoor unit electrical cover with a screwdriver 
    through the hole, remove the terminal block cover by 
    hand and remove the cable clamp by loosening the 
    screws
3. Pass the connecting wires from the back of indoor unit 
    and connect to the indoor terminal block.

Front panel

The drain line must not have a trap anywhere in 
its length, must pitch downwards, and must be 
insulated up to the outside wall.

Drainage

Do not put drain end into water

Proper

Do not form a rise

Step 7: Wrap Pipe and Cable

Step 8: Hang the Indoor Unit

1. Run refrigerant lines through hole in the wall.
2. Hang indoor unit on upper hook of mounting plate, 
then push lower part of indoor unit up on wall to lower 
hook.
3. Move indoor unit from side to side, up and down to 
check if it is hooked securely.

Hang The Indoor Unit

For proper orientation of the refrigerant piping, 
electrical cable and drain lines, refer to below Fig:
- Place the drain hose below the refrigerant piping.
- Make sure that the drain hose is not heaved or 
snaked.

Wrap The Pipe

Indoor unit

Electrical

cable

Drain hose

Heat insulation
type

  Refrigerant piping

Pipe room

Ponding box

2.1 INDOOR UNIT MOUNTIN PLATE

2.2 INSTALLATION PROCESS

2. INDOOR UNIT INSTALLATION

2

INDOOR UNIT INSTALLATION

Electrical cover

Open the cover 

from this hole

Connector for wired controller

(optional,come out from display box)

Electrical cover

Terminal Block Cover

Cable Clamp

30

Wedge

Note: When the gas side connective pipe is Ф16mm(5/8in) or more, the pipe hole should be 90mm(3.54in).

Drill a 65mm or 90mm

(depending on models)
hole on the wall which
is slightly tilted towards
the outside.

The connector parts of connective pipe must 
be placed outside of room.

CAUTION

192

232

426

128

43

Left rear side 
refrigerant

pipe hole φ65

 

Right rear side
refrigerant pipe 

hole φ65

Indoor unit 
outline

43

43

Unit: mm

(A: 802, B:297)

GB

A

B

Summary of Contents for 38HV09JS8C

Page 1: ...5 620 114 Document non contractuel Dans le souci constant d am liorer son mat riel CIAT se r serve le droit de proc der sans pr avis toutes modifications techniques Non contractual document With the t...

Page 2: ...imination 1 Votre municipalit a mis en place des syst mes de collecte gr ce auxquels les utilisateurs peuvent se d barrasser de leurs d chets lectroniques gratuitement 2 Lorsque vous achetez un nouvea...

Page 3: ...tion Ne modifiez pas cet appareil en retirant une protection ou en contournant les dispositifs de verrouillage de s curit Il convient que les travaux lectriques soient effectu s en conformit avec le m...

Page 4: ......

Page 5: ...3 Percer le trou dans le mur tape 8 Suspension de l unit int rieure Raccordement des c bles int rieurs 1 Soulevez le panneau avant de l appareil int rieur 2 Ouvrez le couvercle des composants lectriqu...

Page 6: ...t te du boulon de fixation mesure plus de 12mm Dimensions de l appareil ext rieur mm Dimensions de montage mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376...

Page 7: ...e cuisine et d autres endroits similaires renforcez l isolation Il convient que la temp rature de r sistance la chaleur de l isolation soit sup rieure 120 C Utilisez des adh sifs sur la partie de racc...

Page 8: ...es uniquement REMARQUE 1 Tous les fils lectriques doivent tre d une dimension conforme au code de c blage lectrique local r gional et national Consultez les codes de construction locaux et le code nat...

Page 9: ...iode o les travaux sont r alis s Il convient que la ventilation permette de dissiper le produit frigorig ne lib r en toute s curit et de pr f rence de le rel cher l ext rieur dans l atmosph re 7 8 V R...

Page 10: ...ATIVES L ENTRETIEN la taille de la charge est adapt e la taille de la pi ce dans laquelle les parties contenant le produit frigorig ne sont install es les appareils de ventilation et les orifices fonc...

Page 11: ...ment pouvant tre stock s ensemble sera d termin par les r glementations locales 7 INFORMATIONS RELATIVES L ENTRETIEN 7 16 PROC DURES DE CHARGEMENT Outre les proc dures conventionnelles de chargement l...

Page 12: ...k shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to access and service this product 5 Any handling of the fluorinated gas in this product such as when...

Page 13: ...from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use the specified cables for electrical connectio...

Page 14: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Page 15: ...ening the screws 3 Pass the connecting wires from the back of indoor unit and connect to the indoor terminal block Front panel The drain line must not have a trap anywhere in its length must pitch dow...

Page 16: ...tdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet The moun...

Page 17: ...ve C D Indoor unit flare nuts Check point of indoor unit Check point of outdoor unit A B C D 4 3 REFRIGERANT PIPE NOTE The refrigerant should be charged from the service port on the outdoor unit s low...

Page 18: ...earth connection for functional purposes only CAUTION 60mm 40mm 10mm Power input cord GND 60mm 40mm 10mm GND Connective Cable W 1 2 S L N Power Input To Indoor W 1 2 S L N Power Input To Indoor W 1 2...

Page 19: ...shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and...

Page 20: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Page 21: ...e labels on the equipment stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommend...

Page 22: ...cos Para su eliminaci n hay varias posibilidades 1 El municipio ha establecido sistemas de recogida en los que se pueden desechar los residuos electr nicos de forma gratuita para el usuario 2 En la co...

Page 23: ...la eliminaci n de cualquiera de las protecciones de seguridad ni se salte ninguno de los interruptores de seguridad El trabajo el ctrico debe llevarse a cabo de acuerdo con el manual de instalaci n y...

Page 24: ......

Page 25: ...Conexi n de cables de la unidad interior 1 Levante el panel frontal de la unidad interior 2 Abra la cubierta de los cables el ctricos de la unidad interior con un destornillador quite la cubierta de...

Page 26: ...nillo de fijaci n debe ser mayor de 12mm Dimensiones unidad exterior mm Dimensiones de montaje mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376 3 2 REQUISIT...

Page 27: ...o usando las herramientas de abocardado tal como se indica a continuaci n Di metro exterior A mm M x M n 6 35 mm 8 7 8 3 9 52 mm 12 4 12 0 12 7 mm 15 8 15 4 15 88 mm 19 0 18 6 19 05 mm 23 3 22 9 4 1 4...

Page 28: ...to incorpora una conexi n de toma de tierra solo para fines funcionales AVISO 1 Todos los cables de alimentaci n deben dimensionarse de acuerdo con el c digo de cableado el ctrico nacional Consulte la...

Page 29: ...a ventilaci n debe dispersar de forma segura todo el refrigerante liberado y expulsarlo preferiblemente a la atm sfera externa 7 8 COMPROBACIONES EN EL EQUIPO DE REFRIGERACI N Cuando se cambien compon...

Page 30: ...o de la sala en la que est n instalados los componentes que contienen refrigerante la maquinaria de ventilaci n y las salidas funcionan adecuadamente y no est n obstruidas si se utiliza un circuito d...

Page 31: ...voque una fuga de la carga de refrigerante El n mero m ximo de equipos que se permiten almacenar juntos estar determinado por las regulaciones locales 7 INFORMACI N PARA EL SERVICIO T CNICO 7 16 PROCE...

Reviews: