3.2 SPACE REQUIREMENT FOR OUTDOOR UNIT 

>30cm

>30cm

>200cm

>60cm

(Wall or obstacle)

Maintain channel

Air outlet

Air inlet

M

P

Air inlet

N

>60cm

Fix with bolt

Single Unit Installation

   Before installation, check strength and horizontality of the base so that abnormal sound does not generate.
   Fix the base firmly with anchor bolts (M10) to prevent it from collapsing.
   Install the foundation and vibration-proof rubbers to directly support the bottom surface of the fixing leg that
   is in contact with the bottom plate of the outdoor unit.

3.4 INSTALL THE OUTDOOR UNIT

100mm

100

300mm

Outdoor unit

Vibration-proof rubber

Anchor bolt (M10)

Drainage (Wide 100mm x Depth 150mm)

Mortar Hole (

Φ

100mm x Depth 150mm)

>200

>50

>300

>300

>30

>60

>200

>30

Parallel connect the two units or above

Parallel connect the front with rear sides.

     Connect the drain outlet with an extension drain hose
     Fit the gasket onto drain outlet.

     Insert the drain outlet into the base pan hole of outdoor unit, and rotate 90 degree to securely assemble them.

3.5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT

unit:cm

unit:cm

Base pan hole 
of outdoor unit

Drain hose
(Field supply)

Gasket

Drain Outlet

The mounting dimensions vary among different outdoor units.
The fixing bolt head diameter should be more than 12mm.

In regions with snowfall and cold temperatures, avoid installing the outdoor unit in areas where it 
can be covered by snow. If heavy snow is expected, a field supplied ice or snow stand and/or 
field supplied-installed wind baffle should be installed to protect the unit from snow accumulation 
and/or blocked air intake. 

CAUTION

3.3 OUTDOOR WIRE CONNECTION

Remove the electrical cover and cable clamp by loosening the screws.
Connect wires to the outdoor terminal block by same sequence to indoor unit.

Electric cover

Wire downwards to prevent
water entering control box.

1

2

S

Terminal Block

Cable Clamp

3. OUTDOOR UNIT INSTALLATION

3. OUTDOOR UNIT INSTALLATION

3.1 OUTDOOR UNIT MOUNTING DIMENSION

Outdoor Unit Dimentsion (mm)

Mounting Dimentsion (mm)

W

H

D

A

B

700

550

275

450

260

770

555

300

487

298

333

363

554

702

800

845

515

540

340

376

GB

W

H

Summary of Contents for 38HV09JS8C

Page 1: ...5 620 114 Document non contractuel Dans le souci constant d am liorer son mat riel CIAT se r serve le droit de proc der sans pr avis toutes modifications techniques Non contractual document With the t...

Page 2: ...imination 1 Votre municipalit a mis en place des syst mes de collecte gr ce auxquels les utilisateurs peuvent se d barrasser de leurs d chets lectroniques gratuitement 2 Lorsque vous achetez un nouvea...

Page 3: ...tion Ne modifiez pas cet appareil en retirant une protection ou en contournant les dispositifs de verrouillage de s curit Il convient que les travaux lectriques soient effectu s en conformit avec le m...

Page 4: ......

Page 5: ...3 Percer le trou dans le mur tape 8 Suspension de l unit int rieure Raccordement des c bles int rieurs 1 Soulevez le panneau avant de l appareil int rieur 2 Ouvrez le couvercle des composants lectriqu...

Page 6: ...t te du boulon de fixation mesure plus de 12mm Dimensions de l appareil ext rieur mm Dimensions de montage mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376...

Page 7: ...e cuisine et d autres endroits similaires renforcez l isolation Il convient que la temp rature de r sistance la chaleur de l isolation soit sup rieure 120 C Utilisez des adh sifs sur la partie de racc...

Page 8: ...es uniquement REMARQUE 1 Tous les fils lectriques doivent tre d une dimension conforme au code de c blage lectrique local r gional et national Consultez les codes de construction locaux et le code nat...

Page 9: ...iode o les travaux sont r alis s Il convient que la ventilation permette de dissiper le produit frigorig ne lib r en toute s curit et de pr f rence de le rel cher l ext rieur dans l atmosph re 7 8 V R...

Page 10: ...ATIVES L ENTRETIEN la taille de la charge est adapt e la taille de la pi ce dans laquelle les parties contenant le produit frigorig ne sont install es les appareils de ventilation et les orifices fonc...

Page 11: ...ment pouvant tre stock s ensemble sera d termin par les r glementations locales 7 INFORMATIONS RELATIVES L ENTRETIEN 7 16 PROC DURES DE CHARGEMENT Outre les proc dures conventionnelles de chargement l...

Page 12: ...k shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to access and service this product 5 Any handling of the fluorinated gas in this product such as when...

Page 13: ...from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use the specified cables for electrical connectio...

Page 14: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Page 15: ...ening the screws 3 Pass the connecting wires from the back of indoor unit and connect to the indoor terminal block Front panel The drain line must not have a trap anywhere in its length must pitch dow...

Page 16: ...tdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet The moun...

Page 17: ...ve C D Indoor unit flare nuts Check point of indoor unit Check point of outdoor unit A B C D 4 3 REFRIGERANT PIPE NOTE The refrigerant should be charged from the service port on the outdoor unit s low...

Page 18: ...earth connection for functional purposes only CAUTION 60mm 40mm 10mm Power input cord GND 60mm 40mm 10mm GND Connective Cable W 1 2 S L N Power Input To Indoor W 1 2 S L N Power Input To Indoor W 1 2...

Page 19: ...shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and...

Page 20: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Page 21: ...e labels on the equipment stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommend...

Page 22: ...cos Para su eliminaci n hay varias posibilidades 1 El municipio ha establecido sistemas de recogida en los que se pueden desechar los residuos electr nicos de forma gratuita para el usuario 2 En la co...

Page 23: ...la eliminaci n de cualquiera de las protecciones de seguridad ni se salte ninguno de los interruptores de seguridad El trabajo el ctrico debe llevarse a cabo de acuerdo con el manual de instalaci n y...

Page 24: ......

Page 25: ...Conexi n de cables de la unidad interior 1 Levante el panel frontal de la unidad interior 2 Abra la cubierta de los cables el ctricos de la unidad interior con un destornillador quite la cubierta de...

Page 26: ...nillo de fijaci n debe ser mayor de 12mm Dimensiones unidad exterior mm Dimensiones de montaje mm W H D A B 700 550 275 450 260 770 555 300 487 298 800 554 333 515 340 845 702 363 540 376 3 2 REQUISIT...

Page 27: ...o usando las herramientas de abocardado tal como se indica a continuaci n Di metro exterior A mm M x M n 6 35 mm 8 7 8 3 9 52 mm 12 4 12 0 12 7 mm 15 8 15 4 15 88 mm 19 0 18 6 19 05 mm 23 3 22 9 4 1 4...

Page 28: ...to incorpora una conexi n de toma de tierra solo para fines funcionales AVISO 1 Todos los cables de alimentaci n deben dimensionarse de acuerdo con el c digo de cableado el ctrico nacional Consulte la...

Page 29: ...a ventilaci n debe dispersar de forma segura todo el refrigerante liberado y expulsarlo preferiblemente a la atm sfera externa 7 8 COMPROBACIONES EN EL EQUIPO DE REFRIGERACI N Cuando se cambien compon...

Page 30: ...o de la sala en la que est n instalados los componentes que contienen refrigerante la maquinaria de ventilaci n y las salidas funcionan adecuadamente y no est n obstruidas si se utiliza un circuito d...

Page 31: ...voque una fuga de la carga de refrigerante El n mero m ximo de equipos que se permiten almacenar juntos estar determinado por las regulaciones locales 7 INFORMACI N PARA EL SERVICIO T CNICO 7 16 PROCE...

Reviews: