![Chroma 62000P Series Operating & Programming Manual Download Page 123](http://html1.mh-extra.com/html/chroma/62000p-series/62000p-series_operating-and-programming-manual_2604534123.webp)
Programmable DC Power Supply 62000P Series Operating & Programming Manual
Syntax:
SOURce:VOLTage:SLEW
<NR1>[suffix]
SOURce:VOLTage:SLEW <NR1>[suffix]
Parameter:
Refer to individual spec for valid numeric range.
Example:
SOUR:VOLT:SLEW 0.01 It sets the output voltage slew rate to
0.01volt/mS
SOUR:VOLT:SLEW 10 It sets the output voltage slew rate to
100 volt/mS
Query Syntax: SOUR:VOLT:SLEW?
Return Parameter: <NR1> [Unit Volt/ms]
Query Example: SOUR:VOLT:SLEW? It returns the voltage slew rate.
Return Example: 10
(5) SOURce: CURRent
Description:
It sets the output current (ampere).
Syntax:
SOURce:CURRent
<NRf+>[suffix]
SOURce:CURRent <NRf+>[suffix]
Parameter:
Refer to individual spec for valid numeric range.
Example:
SOUR:CURR 1 It sets the output current to 1 amps.
SOUR:CURR 60.00 It sets the output current to 60.00 amps.
Query Syntax: SOUR:CURR?
Return Parameter: <NRf+> [Unit Amp]
Query Example: SOUR:CURR?
It returns the current.
Return Example: 9.000000e1
(6) SOURce:CURRent:LIMit:{HIGH/LOW}
Description:
It sets the output current range.
Syntax:
SOURce:CURRent:LIMIT:HIGH
<NRf+>[suffix]
SOURce:CURRent:LIMIT:LOW <NRf+>[suffix]
Parameter:
Refer to individual spec for valid numeric range.
Example:
SOUR:CURR:LIMIT:HIGH 60.0 It sets the output current range
to 60A maximum.
SOUR:CURR:LIMIT:LOW 20.0 It set the low limit to 20A for
current output protection.
Query Syntax: SOUR:CURR:LIMIT:HIGH?
SOUR:CURR:LIMIT:LOW?
Return Parameter: <NRf+> [Unit Amp]
Query Example: SOUR:CURR:LIMIT:HIGH? It returns the maximum range set
for current.
Return Example: 60.00
(7) SOURce:CURRent:PROTect:{HIGH }
Description:
It sets the current range for over current protection.
Syntax:
SOURce:CURRent:PROTect:HIGH <NRf+>[suffix]
Parameter:
Refer to individual spec for valid numeric range.
Example:
SOUR:CURR:PROT:HIGH 60.0 It sets the high limit to 60Amp
for current output protection.
Query Syntax: SOUR:CURR:PROT:HIGH?
Return Parameter: <NRf+> [Unit Amp]
Query Example: SOUR:CURR:PROT:HIGH?
It returns the high limit of
5-12