Appendix A: Features and Specifications
34
ONEAC Sinergy SE II Series UPS User Manual
*
Optional ten foot power cord available (4 kVA - 10’ power cord with L6-30P; 6 kVA - 10’ power cord with 6-50P). Call ONEAC for details,
Table 14. Specifications
UPS Model
SE041
SE061
SE081
SE101
Table 15. SE II Series UPS Typical UPS Runtimes
Model Number
Internal Battery
Internal Battery
Plus 1 Ext
Battery
Per Power
Head
Internal Battery
Plus 2 Ext
Battery
Per Power Head
SE041 half load/full load (min)
37/15
156/66
310/130
SE061 half load/full load (min)
21/9
84/39
175/78
SE081 half load/full load (min)
21/6
73/23
140/45
SE101 half load/full load (min)
13/5
60/18
117/35