You can preload values into Data Arrays using the
configuration file. The FieldServer configuration
manual has notes on how to do that.
FSU_ESC:#4 Err. MSG command out of
range. %s[%d]Value=%d
Where %s[%d] specifies a Data Array and
offset.
Valid Entries in the Data Array are 1-16 for Msgs A-
P
The most likely cause for this message is either the
driver has started up and there are zero’s in the
Data Arrays or the other protocol has written a
number to the FieldServer that is out of the valid
range.
You can preload values into Data Arrays using the
configuration file. The FieldServer configuration
manual has notes on how to do that.
FSU_ESC:#5 Err. MSG command not
recognized. (%s)
The Message command speficied in the
configuration file must be ‘MSG’ you cannot
specify ‘MSG_A’ or any other format. Re
ad
example 3 in chapter 4 for example on how to
configure this command.
Correct the configuration and then download the
corrected configuration file and reset the
FieldServer for the changes to take effect.
FSU_ESC:#6 Err. PHASE command out of
range. %s[%d]Value=%d
Where %s[%d] specifies a Data Array and
offset.
Valid Entries in the Data Array are 1 or 2 for
PHASE+ or PHASE-
The most likely cause for this message is either the
driver has started up and there are zero’s in the
Data Arrays or the other protocol has written a
number to the FieldServer that is out of the valid
range.
You can preload values into Data Arrays using the
configuration file. The FieldServer configuration
manual has notes on how to do that.