FS-8705-12 Federal Signal Ultravoice - Electronic Siren Controllers Driver Manual
Page 9 of 30
© 2021 CHIPKIN AUTOMATION SYSTEMS
4
Configuring the FieldServer as a FSC - Electronic Siren Controllers Serial Driver Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files included
with the FieldServer (See “.csv” sample files provided with the FS).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a
FSC - Electronic Siren Controllers Serial Driver Server.
4.1
Data Arrays/Descriptors
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the
FieldServer for FSC - Electronic Siren Controllers Serial Driver communications, the driver independent FieldServer buffers
need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side
Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section.
Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
SECTION TITLE
Data_Arrays
COLUMN TITLE
FUNCTION
LEGAL VALUES
Data_Array_Name
Provide name for Data Array
Up to 15 alphanumeric
characters
Data_Array_Format
Provide data format. Each Data Array
can only take on one format.
Float, Bit, UInt16, Uint32,
SInt16, Packed_Bit, Byte,
Packed_Byte,
Swapped_Byte
Data_Array_Length
Number of Data Objects. Must be
larger than the data storage area
required by the Map Descriptors for
the data being placed in this array.
1-10,000
Example
// Data Arrays
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length,
DA_AI_01,
UInt16,
200
DA_AO_01,
UInt16,
200
DA_DI_01,
Bit,
200
DA_DO_01,
Bit,
200