74
1 None
2 Dispatch
3 QReactSet
4 PF Set
→
5 PF(P) Curve
6 Q(U) Curve
Figure 5-16 Reactive power mode
1). None
:
No mode/disable reactive power mode
2). Dispatch
:
Remote power dispatch mode
Note: The ActivePower, PF and Q value can be adjusted by remote software if
the
“Dispatch” is selected.
3). QReactSet
:
Set the Q value
Note: Change the reactive power by adjusting the Q value (reactive
compensation)
4). PF Set
:
Set the PF value
Note: Change the reactive power by adjusting the PowerFactor
5). PF(P) Curve
:
PF curve mode
Note: The power factor changes according to the power change, as shown in
Figure 5-17:
INSTRUCTION:
The PF (P) Curve function is only available for VDE-4105 and CEI
0-21 grid standard.