Possible causes:
1.Ambient temperature outside the inverter is too
high;
2.Fan is blocked;
3.
Convection airflow is insufficient due to improper
installation.
Recommended solutions:
1.Confirm that external ambient temperature is
within the specified range of operating temperature;
2.Check whether air inlet is blocked;
3.Check whether fan is blocked;
4.Check whether the location of installation is
appropriate or not;
5.Observe for 30 minutes and see whether the
alarm will be eliminated automatically;
6.Contact after-sales service personnel
2.GridV.OutLim
Definition:
Grid voltage exceeds the specified range,
Possible causes:
1.Grid voltage is abnormal;
Power grid breaks down
2.Cable connection between the inverter and the
grid is poor;
Recommended solutions:
1.Observe for 5 minutes and see whether the alarm
will be eliminated automatically;
2.Check whether the grid voltage is within the
specified range;