Chapter 8 Technical Data
Model Name
CPS
SCA20KTL-DO
CPS SCA25KTL-DO
DC Input
Nominal DC Input Power
21kW
26kW
Max. DC Input Power for
each MPPT
12kW
14kW
Max. DC Input Voltage
1
1000Vdc
Operating DC Input Voltage
Range
300-900Vdc
Start-up DC Input Voltage /
Power
330V/300W
Nominal DC Input Voltage
635Vdc
Number of MPP Trackers
2
MPPT Voltage Range
400-800Vdc
Max. Input Current
2x 27A
2x 32A
Isc PV(absolute max)
2x 41A
2x 48A
Max. inverter backfeed
current to the array
0 A
Number of DC Inputs
4 stringsx2
DC Disconnection Type
Integrated DC switch
AC Output
Rated AC Output Power
20kW
25kW
Max. AC Output Power
20kW
25kW
Rated Output Voltage
400/230Vac
Output Voltage Range
2
320-460Vac
Grid Connection Type
3Φ/ N / PE
Max AC Output Current
32A
40A
AC Inrush Current
149A Peak@211us
Maximum Output Fault
Current
L-N/PE 100A Peak@320ms,
56.6A RMS@20ms
L1/L2/L3 158A Peak@992ms,
1
Exceeding the Max. DC Input Voltage may cause permanent damage to the equipment.
2
The Output Voltage Range may differ according to specific grid standard.