P-Parameters
P47
Night Mode Validation (Night Mode:
DHW Increase 3C)
0
(
Off
)、
1
(
On
)
0
P48
Night Mode Starting Time
0-23
(
Time
)
22
P49
Night Mode Ending Time
0-23
(
Time
)
6
P50
Flow Switch Minimum Enabled Water Flow Switch On
(CN5)
6~60L/Min
6
P51
Local RS485 Address
0~99
1
P52
Water Flow Switch Type
0: No Water Flow Switch 1: YF-G1 Water Flow Meter
"Black" 2:YF-DN50 Waterflow Meter "Not Used"
3:SEN-HZG1WA Copper Waterflow Meter
3
P53
Virus Killing Function Validation
0= Invalid; 1= Valid
0
P54
Cooling Function Validation
0= Invalid; 1= Valid
1
P55
Heating Function Validation
0= Invalid; 1= Valid
1
P56
DHW Function Validation
0= Invalid; 1= Valid
1
P57
Air Source Or Geo Source Selection
0= Invalid; 1= Valid
0
P58
Solar Source Validation
0= Invalid; 1= Valid
0
P59
Simple Or Inverter HP Selection
0= Simple; 1= Inverter Type
1
P60
Indoor PCB Enable Not Applicable
0= Invalid; 1= Valid
0
P61
Fan Selection
0= AC Fan; 1=DC Fan
0
P62
Heating Fan Highest Speed
71~100
80
P63
Fan Lowest Speed
30~70
50
P64
Manual Set Fan Speed
30~100
50
P65
DC Fan Speed Adjustment Temp For Heating
2-15
℃
4
P66
DC Fan Speed Adjustment Temp For Cooling
3-18
℃
5
P67
C4 Water Pump Selection
0: Normal 1:PWM
1
P68
C4 Water Pump Water Temp Difference
Range:1-10
5
P69
C4 Lowest Water Pump Speed
Range:2-8
4
P70
Restore Default Parameter
0: Normal 1: Restore Once
0
P73
G4 Heat Recovery Valve Selection
0:Parallelly 1: Serially 2 Free Cooling
0
P74
SSR Increase To Max Delay Time
1~20 Minutes
10
P80
Virus Killing Once
0: No 1: Kill Once
0
P81
Virus Killing Interval Days
X: 7
-
99 Days
7
P82
Virus Killing Start Time
Y: 0
-
23
1
P83
Virus Killing Duration Time
Z: 5
-
99 Minutes
10
P84
E2 Start Delay Time
5~15 Minutes
15
P85
Heat Recovery Module Enable (Not Used)
0= Invalid; 1=valid (Out16=heat Recovery Water Pump)
0
P89
Temp Unit
0=c; 1=f
0
P90
E2 Capacity * 100W
0-255
50
P91
E2 Rated Voltage V
0~250
230
P92
E2 Heat Exchange Factor
0~600
500
P93
E2 Voltage Compensation V
-20~20v
0
P94
Cooling Temp Range (If Set To 1, Must Use Enough Glycol) 0:10~25; 1:0~25
0
P95
AC Antifreeze Start Temp
-15~7
5
P96
AC Heating Mini Frequency
30~50
30
P97
AC Cooling Fan Max Speed
71~100
80
P98
Free Cooling Start Air Temp
-16~20c
5
P99
Free Cooling Temp Difference
3~15c
5
P100
Error Reset
0: Not Reset; 1: Reset Once
0
P101
Resonance Range Bottom Point
30~p102
100
P102
Resonance Range Top Point
P101~44
100
P103
Heating Mode Start Air Temp
0~17
0
P104
Cooling Mode Start Air Temp
0~25
0
P105
EEV Max Degree When C19<40
50~240
240
Summary of Contents for CX34-4
Page 4: ...Chiltrix Inc www chiltrix com CX34 Components 4 ...
Page 18: ...Chiltrix Inc www chiltrix com Electric Connections and Component Locator 18 ...
Page 19: ...Chiltrix Inc www chiltrix com CX34 System Wiring Diagram 19 ...
Page 25: ...Chiltrix Inc www chiltrix com G3 VALVE Seasonal Switch Valve G3 Ports 25 ...
Page 34: ...Chiltrix Inc www chiltrix com 34 Language Screen Screen Saver ...
Page 35: ...Chiltrix Inc www chiltrix com 35 Touch Screen Fixing Calibration Time Setting ...
Page 52: ...Chiltrix Inc www chiltrix com 52 ...