P-Parameters
LCD
Description
Meaning
Default
P00
Auto Restart After Power Off
0
:
Invalid
;
1
:
Valid
1
P01
DHW Hot Water Temp Hysteresis Temp
2~15
℃
,
Minus Hysteresis
2
℃
P02
AC Temp Hysteresis Temp
2~15
℃
,
Minus Hysteresis
2
℃
P03
Coil Copper Pipe Temp To Active Defrost
-20~5
℃
0
℃
P05
Temp 2 To Active Defrost
-20~0
℃
-5
℃
P06
Coil Copper Pipe Temp To Stop Defrost
10~35
℃
30
℃
P07
Defrost Duration Time
15~99 Minutes
30
P08
Defrost Interval Time
15~99 Minutes
35
P09
Ambient Temp To Activate E1 DHW E-heater
-20~20
℃
0
℃
P10
Ambient Temp To Activate E2 AC E-heater
-20~20
℃
0
℃
P11
DHW Frequency Limitation Percentage
2~10 (= Highest Frequency* 20~100%)
10
P12
Compressor Discharge Air Protection Temp
100~127
℃
100
℃
P13
Defrost Interval Multiple Times Control
0
:
No Defrost 1~4
;
Defrost Interval Time Multiple Rate
1
P14
G3 Valve Function Selection
0
:
G3 Is Seasonal Switching Valve 1
:
G3 is Solar Valve
0
P15
Cooling Target Temp
10~25°c
12
P16
Heating Target Temp
(Au)10~55°c
45
P17
DHW Target Temp
(Au)10~55°c
50
P18
Sterilization Target Temp
65
P19
Fixed Speed At Manual Speed Control (For Factory Testing
Only)
10~100 Hz
50hz
P20
Running Frequency Control Set
(For Factory Testing Only)
0
:
Manual Frequency
;
1
:
Auto Running Frequency
1
P21
EEV Manually Initial Open Degree (Heating)
40~480 When P23=0,1,2 It Is Fixed Degree, When P23=3, It
Is Initial Open Degree
350
P22
EEV Manually Initial Open Degree (Cooling)
40~480 When P23=0,1,2 It Is Fixed Degree, When P23=3, It
Is Initial Open Degree
350
P23
EEV Control Mode
0=No
;
1=Checking Table
;
2=Manual
;
3=Auto
3
P24
EEV Over Heat Temp (Heating)
-5~10
℃
For Factory Only
0
℃
P25
EEV Over Heat Temp (Cooling)
-5~10
℃
For Factory Only
0
℃
P26
Water Pump Working Mode
0 = (Not Stop) 1 = Stop When Reach Temp
、
2 = Run 1 Minute Every 15min.
0
P27
Second Heat Source Function
0: Invalid, 1: Normal 2nd Heat Source, 2: Together With
E2, 3: Together With Gas Boiler
0
P28
Starting Air Temp For Second Heat Source
-30~15
℃
(On When Lower Than This)
-15
℃
P29
Room Target Temp
10-28
℃
21
℃
P30
EEV Minimum Open Degree
40~200
80
P31
EEV Minimum Open Degree1
40~200
80
P33
Start Defrost Air - Coil Temp Difference
0~40
℃
8
℃
P36
Compressor Max Speed
10-200
80
P45
AC AU Curve Offset Value (Our Weather Compensation
Curve AU)
-15~15
℃
0
℃
P46
AC AU Curve Max Temp Value (Our AU)
30~50
℃
45
Summary of Contents for CX34-4
Page 4: ...Chiltrix Inc www chiltrix com CX34 Components 4 ...
Page 18: ...Chiltrix Inc www chiltrix com Electric Connections and Component Locator 18 ...
Page 19: ...Chiltrix Inc www chiltrix com CX34 System Wiring Diagram 19 ...
Page 25: ...Chiltrix Inc www chiltrix com G3 VALVE Seasonal Switch Valve G3 Ports 25 ...
Page 34: ...Chiltrix Inc www chiltrix com 34 Language Screen Screen Saver ...
Page 35: ...Chiltrix Inc www chiltrix com 35 Touch Screen Fixing Calibration Time Setting ...
Page 52: ...Chiltrix Inc www chiltrix com 52 ...