background image

Section 360-880-202

11

4.5.3. Timeslot Allocated on the Secondary T1 Circuit

When a timeslot is allocated from the secondary T1 to a channel, the timeslot mode of the secondary T1 timeslot

is ignored and does not affect the data routing.  Data is routed from the allocated channel to and from the time

slot on the secondary T1 circuit.   If the timeslot on the primary T1 is set to idle, the output data for the timeslot on

the primary T1 will be an all ones (11111111) which equates to an “idle” signal.  If the time slot on the primary T1 is

set to broadcast, then the output data on the primary T1 for the timeslot will be the same data that is sent from

the secondary T1 to the allocated channel.  This allocation is called Broadcast mode because, the data from the

timeslot on the secondary T1 circuit is broadcast to the channel and to the primary T1 timeslot.

Primary

Secondary

W

D/I

E

Controlled by Primary T1 Time Slot Mode

Figure 12.  Drop at T1 Secondary with No Drop on Primary

4.5.4. Non-Allocated Timeslots

When a timeslot is not allocated to either the primary T1 circuit or the secondary T1 circuit, the primary and sec-

ondary timeslot mode determines the data output on the respective T1. If the mode is set to idle, the output of the

timeslot will be an all ones (11111111) which equates to an “idle” signal.  If the mode is set to broadcast then the

output of the timeslot on the T1 will be the data from the corresponding time slot on the other T1.  This allocation

mode is referred to as “Pass Through” because, when both primary and secondary timeslot modes are set to

broadcast the data passes through the 360-80.

Primary

Secondary

W

D/I

E

Controlled by Secondary TS Mode

Controlled by Primary TS Mode

Figure 13.  No Drop at T1 Primary or Secondary

4.6

Forced Bypass (Manually Selected via Management Normal Mode Only)

If this option is selected for an ICB, it will require local intervention at the site of the ICB to reset.

Restoring normal error free operation of the ICB will require a “reset” to return to stored values on a

local craft interface or Ethernet connection, or removing both the T1-S and ST1U. The cards must

then be reinserted in order, first the T1-S, followed by the ST1U.

WARNING

Card configuration is stored in an EEPROM so no additional settings adjustments are required.

4.7

Facility Alarm Handling

The alarm timing circuit provides the indications and timing for the trunk processing. Hit integration for Frame

Loss (FRL) is provided to prevent trunk processing during intermittent frame losses. LEDs are provided for local

red alarm (AR) and remote yellow alarm (AY).
The T1-S provides three optional trunk processing timing options (both primary and secondary T1s are configured

the same) that are selected via the NMS software. In the NORMAL position, the unit provides standard D4 timing.

In the CM2 & CM3 positions, special shortened timings are provided.
When a loss of signal or framing is detected on the WEST receive facility, a Red Alarm (AR) is declared and the

WEST AR LED is illuminated after 2.5 seconds (1 second if CM2 option is selected or immediately if the CM3

option is selected), and the unit will begin its trunk processing routine. This causes the following:

Summary of Contents for 3608-80 Secondary T1

Page 1: ...subject to change without notice Page 1 of 18 3608 80 Secondary T1 Unit CONTENTS PAGE Part 1 GENERAL 2 Part 2 INSPECTION 3 Part 3 APPLICATION GUIDELINES 4 Part 4 CIRCUIT DESCRIPTION 7 Part 5 INSTALLA...

Page 2: ...ependent T1 loop timing dual T1 mode only Transport Protection switching protection mode only Drop and re insert operation with bypass normal D RI mode only Front panel status LEDs Front panel T1 moni...

Page 3: ...tion Red AR Alarm Status LED Yellow AY Alarm Status LED Loss of frame LOF Alarm Status Loss of signal LOS Alarm Status Power status LED T1 framing selected Line code Trunk processing TP status LED Lin...

Page 4: ...and the T1 of the ST1U to be connected to two different 360 80 ICBs These two T1s run independently of each other and allow the 360 80 system to provide up to 1 5 Mbps to each T1 for a total of over...

Page 5: ...switch to the protection mode See Figure 4 for a typical configuration Note Both T1 S units should be set for the same error threshold 360 80 Primary T1 360 80 T1 Protection T1 S ST1U T1 S ST1U Figure...

Page 6: ...Re Insert 8 channels west and 8 channels east Drop Re Insert 16 channels Terminate 360 80 ICB 360 80 ICB 360 80 ICB A B C West East Site 1 Site 2 8 channels west Figure 6 Drop and Re Insert Applicati...

Page 7: ...lay path for the T1 facility as part of the assembly as shown in Figure 8 When de energized these relays bypass the ICB and connect the WEST primary T1 to the EAST secondary T1 When the ST1U and T1 S...

Page 8: ...des monitor jacks to monitor this T1 The T1 then goes to the EAST TIMING and FRAMING block where the circuit detects either SF or ESF framing A loss of framing signal will cause the AR LED to light an...

Page 9: ...stalled card will be allocated to phantom channels These timeslots must be de allocated before they can be allocated to a channel When a different card is inserted into a chassis slot that had timeslo...

Page 10: ...serted between the channel and the same timeslot of the other T1 Primary Secondary W D I E Time Slot Mode has No Effect on Data in Both Directions Figure 10 Drop at T1 Primary and Secondary for the Sa...

Page 11: ...ass Through because when both primary and secondary timeslot modes are set to broadcast the data passes through the 360 80 Primary Secondary W D I E Controlled by Secondary TS Mode Controlled by Prima...

Page 12: ...no other action is taken Red or yellow alarms detected on the East facility will illuminate the respective AR and or AY LEDs When the red alarm condition no longer exists for approximately 15 seconds...

Page 13: ...tem 6 After the self test is performed check the software provisioning of the unit using either the front panel craft interface on the front of the controller unit or the network management interface...

Page 14: ...ible indications of present alarm conditions it does NOT clear the alarm If a new alarm occurs the audible indication will re enable Table 1 LED Definitions Label Color Indicates that POWER Green The...

Page 15: ...ction Line Near End Line Far End Payload Far End None Remote Control Method None Occupy One Channel Facility Data Link ESF Format Only Facility Data Link Bypass Drop and Re insert Only Auto Bypass For...

Page 16: ...arton in which the replacement was shipped using the pre addressed shipping label provided Call your customer service representative at the telephone number above for more details 9 4 Standard Repair...

Page 17: ...to monitor the secondary T1 signal both transmit and receive without interference Alarm interface and contacts The system provides visual and audible alarm contact clo sure when the channel bank is i...

Page 18: ...3 Physical Specifications Feature U S Metric Height 0 75 inch 1 9 centimeters Width 5 64 inches 14 32 centimeters Depth 9 25 inches 23 49 centimeters Weight 0 64 pound 290 grams Temperature 40 to 149...

Reviews: