background image

Section 360-880-202

7

4.

CIRCUIT DESCRIPTION

Figure 8 shows a block diagram of the ST1U, and its relationship to other elements of the 360-80 ICB.

4.1

Normal (Drop and Re-Insert) Mode Configuration

The T1-S provides the centralized control, multiplexing and test features for the 360-80 ICB. T1 signals from and

to the WEST (primary T1) direction are first routed through the ST1U to the T1-S. The ST1U uses timing from the

T1-S and must be loop timed to the WEST to operate correctly.
T1 signals from and to the EAST (secondary T1) direction are routed to the ST1U. The ST1U includes a monitor

jack access to the T1.
The ST1U provides a bypass relay path for the T1 facility as part of the assembly, as shown in Figure 8. When

de-energized, these relays bypass the ICB and connect the WEST (primary) T1 to the EAST (secondary) T1.

When the ST1U and T1-S are installed and functioning properly, these relays are energized. Figure 8 shows the

relay contacts in this mode. If either of these modules fail or the T1-S is removed, the relay will release and by-

pass the T1. The ST1U can also be manually selected to bypass the T1.
The ST1U provides various front panel indicators to monitor operation .

X
M
T
R

C

V

MON

WEST

PROTECTION

BYPASS

CONTROL

X
X
X
X

X
X
X
X

EAST

TIMING &

FRAMING

TIMESLOT

CONTROL

CABLE

TO

T1-S

VOICE & DATA CIRCUITS

T1 (J6)

PRIMARY

During normal operation bypass,

relay is energized as shown.

EAST

T1 (J4)

SECONDARY

(J5)

T1-S

T1-S

BYPASS

CIRCUIT

Figure 8.  Secondary T1 Unit Block Diagram

Summary of Contents for 3608-80 Secondary T1

Page 1: ...subject to change without notice Page 1 of 18 3608 80 Secondary T1 Unit CONTENTS PAGE Part 1 GENERAL 2 Part 2 INSPECTION 3 Part 3 APPLICATION GUIDELINES 4 Part 4 CIRCUIT DESCRIPTION 7 Part 5 INSTALLA...

Page 2: ...ependent T1 loop timing dual T1 mode only Transport Protection switching protection mode only Drop and re insert operation with bypass normal D RI mode only Front panel status LEDs Front panel T1 moni...

Page 3: ...tion Red AR Alarm Status LED Yellow AY Alarm Status LED Loss of frame LOF Alarm Status Loss of signal LOS Alarm Status Power status LED T1 framing selected Line code Trunk processing TP status LED Lin...

Page 4: ...and the T1 of the ST1U to be connected to two different 360 80 ICBs These two T1s run independently of each other and allow the 360 80 system to provide up to 1 5 Mbps to each T1 for a total of over...

Page 5: ...switch to the protection mode See Figure 4 for a typical configuration Note Both T1 S units should be set for the same error threshold 360 80 Primary T1 360 80 T1 Protection T1 S ST1U T1 S ST1U Figure...

Page 6: ...Re Insert 8 channels west and 8 channels east Drop Re Insert 16 channels Terminate 360 80 ICB 360 80 ICB 360 80 ICB A B C West East Site 1 Site 2 8 channels west Figure 6 Drop and Re Insert Applicati...

Page 7: ...lay path for the T1 facility as part of the assembly as shown in Figure 8 When de energized these relays bypass the ICB and connect the WEST primary T1 to the EAST secondary T1 When the ST1U and T1 S...

Page 8: ...des monitor jacks to monitor this T1 The T1 then goes to the EAST TIMING and FRAMING block where the circuit detects either SF or ESF framing A loss of framing signal will cause the AR LED to light an...

Page 9: ...stalled card will be allocated to phantom channels These timeslots must be de allocated before they can be allocated to a channel When a different card is inserted into a chassis slot that had timeslo...

Page 10: ...serted between the channel and the same timeslot of the other T1 Primary Secondary W D I E Time Slot Mode has No Effect on Data in Both Directions Figure 10 Drop at T1 Primary and Secondary for the Sa...

Page 11: ...ass Through because when both primary and secondary timeslot modes are set to broadcast the data passes through the 360 80 Primary Secondary W D I E Controlled by Secondary TS Mode Controlled by Prima...

Page 12: ...no other action is taken Red or yellow alarms detected on the East facility will illuminate the respective AR and or AY LEDs When the red alarm condition no longer exists for approximately 15 seconds...

Page 13: ...tem 6 After the self test is performed check the software provisioning of the unit using either the front panel craft interface on the front of the controller unit or the network management interface...

Page 14: ...ible indications of present alarm conditions it does NOT clear the alarm If a new alarm occurs the audible indication will re enable Table 1 LED Definitions Label Color Indicates that POWER Green The...

Page 15: ...ction Line Near End Line Far End Payload Far End None Remote Control Method None Occupy One Channel Facility Data Link ESF Format Only Facility Data Link Bypass Drop and Re insert Only Auto Bypass For...

Page 16: ...arton in which the replacement was shipped using the pre addressed shipping label provided Call your customer service representative at the telephone number above for more details 9 4 Standard Repair...

Page 17: ...to monitor the secondary T1 signal both transmit and receive without interference Alarm interface and contacts The system provides visual and audible alarm contact clo sure when the channel bank is i...

Page 18: ...3 Physical Specifications Feature U S Metric Height 0 75 inch 1 9 centimeters Width 5 64 inches 14 32 centimeters Depth 9 25 inches 23 49 centimeters Weight 0 64 pound 290 grams Temperature 40 to 149...

Reviews: