11

LAMP REPLACEMENT PROCEDURE

Unplug unit from the electrical outlet before starting replacement procedure. 

NOTE:  

Wear oil-free cotton gloves prior to procedure in case of accidental breakage of glass. 

1. Rotate the CX-Aire ballast assembly counterclockwise

until it stops (Figure 19).

2. Remove  the  ballast  assembly  and  lamp  from  the

mounting base (Figure 20).

3. Remove the lamp from the lamp socket (Figure 21). 
4. Install the replacement lamp into lamp socket. Do not

handle the lamp with bare hands. Oils on the hands
tend to reduce lamp intensity. 

5. Wipe off the glass with the supplied alcohol wipe. 
6. Position the ballast assembly power cord 90 degrees

to the viewport hole on the mounting base and press
the ballast against the mounting base. Rotate the
ballast assembly clockwise until it stops and is locked
in place (Figure 22). 

7. After  assembly  is  firmly  in  place,  plug  the  power

supply cord back into the standard electrical outlet.
Check lamp operation by looking through the viewport
hole. A blue glow should be seen in the duct. 

8. After  replacing  the  lamp,  make  sure  to  install  the

Lamp Replacement Label. Print the date on the label
and apply to the side of ballast assembly. 

NOTE:

If  blue  light  leaks  through  any  portion  of

plenum  and/or  around  mounting  plate,  unplug
power  supply  cord  immediately  and  seal  affected
areas and/or rotate ballast and repeat step #6 above. 

9. UVC lamps contain a small amount of mercury, like a

typical fluorescent lamp. Check with your local waste
management authority for local disposal or recycling
requirements. 

Never touch broken lamp or internal

contents of lamp. The lamp contains mercury.

NOTE:

In case of accidental exposure to internal contents

of  lamp,  wash  hands  and  any  other  affected  skin  area
with a mild detergent.  Remove affected clothing imme-
diately.  If skin surface is pierced, seek medical attention
immediately.

WARNING

WARNING

Rotate
clockwise

Viewport
hole

Ballast assembly

Lamp sockets

Insert lamp

Remove lamp

Long pin must
be inserted in
position shown

Proving
switch

Remove
ballast assembly

Clean lamp glass with alcohol wipe

then insert

ballast assembly

Rotate
counter
clockwise

Viewport
hole

Figure 22

Figure 21

Figure 20

Figure 19

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC

light may cause permanent eye damage or blindness. Never operate the CX-Aire Air Purifying System
out of the plenum. Avoid touching the glass portion of the lamp with your hands.

WARNING

Summary of Contents for CX-AIRE

Page 1: ...Installation Maintenance CX AIRE IN DUCT AIR PURIFIER READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE...

Page 2: ...ercury After opening the carton unpack and inspect the unit and lamp for damage Do not install this unit if any damage is noticeable If lamp is damaged cracked or broken do not touch lamp or other con...

Page 3: ...ended For larger applications multiple units are recommended BEFORE INSTALLATION READTHESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Disconnect and lock out power s...

Page 4: ...as possible to the AC coil Figure 1 E Mount the UV lamp unit not less than 181 ft in the line of sight to any openings in the air duct and not less than 44 ft in the line of sight to any non metallic...

Page 5: ...STALLATION STEP 2 MOUNTING TEMPLATE OR DUCTBOARD ADAPTER PLATE A or B NOTE If installing on sheet metal air duct follow step A using the the supplied mounting template If mounting onto a fiberglass du...

Page 6: ...ure 4 a Mount the supplied metal mounting plate onto the duct with duct tape in either a vertical or horizontal position Figure 5 b Bend tabs outward Figure 6 c Using a knife or blade cut out a rectan...

Page 7: ...at the UVC light may cause permanent eye damage or blindness Never operate the CX Aire Air Purifying System out of the plenum Avoid touching the glass portion of the lamp with your hands WARNING INST...

Page 8: ...on a suitable location the mounting screw head cannot be in the shaded area of template Figure 14 B Press shield onto duct wall Then secure with 2 sheet metal mounting screws Figure 15 STEP 4 MOUNTIN...

Page 9: ...ided Plug the power supply cord into a standard 120VAC electric outlet Check lamp operation by looking through the viewport hole NOTE The viewport hole is made of glass and will not allow any UVC rays...

Page 10: ...up rotate ballast slightly clockwise or counterclockwise 5 If lamp does not light up after rotating ballast replace lamp 6 If unit still does not light up after replacing lamp replace unit RECOMMENDE...

Page 11: ...el and apply to the side of ballast assembly NOTE If blue light leaks through any portion of plenum and or around mounting plate unplug power supply cord immediately and seal affected areas and or rot...

Page 12: ...ives electrical controls and other components manufactured for Vendor by others are not covered by these warranty provisions All warranty claims must be processed through point of purchase All warrant...

Reviews: