18.13 Technical data
All models are power supplied 230V 50Hz.
Model
PRIMARY SIDE
SECONDARY SIDE
(SS/DS/DD models only)
3 port
Valve
DN
Valve
Kvs
Pump type
Imax
(A)
Pmax
(W)
Pump type
Imax
(A)
Pmax
(W)
EFF52/EFB60
32
16
Magna 3(D)
32-80
1,2
144
Magna 3
32-40N
0,61
74
EFF76/EFB112
40
25
Magna 3(D)
40-100
1,61
361
Magna 3
32-100N
1,47
180
EFP3000
25
10
Magna 3(D)
40-60
1,47
178
Magna 3
32-40N
0,61
74
EFP5000
40
25
Magna 3(D)
40-60
1,47
178
Magna 3
32-40N
0,61
74
EFP7000/EFP9000
40
25
Magna 3(D)
40-120
1,95
440
Magna 3
32-100N
1,47
180
Model
Direct (Inst.)*
Indirect (S.I.)*
Max Weight
Max Dim (LxWxH)
Total Electrical Consumption
(kg)
(mm)
EFF52/EFB60
1.8 A
159 W
2.41 A
233 W
86
480x540x1450
EFF76/EFB112
2.21 A
376 W
3.68 A
556 W
135
590x660x1450
EFP3000
2.07 A
193 W
2.68 A
267 W
191
505x850x1315
EFP5000
2.07 A
193 W
2.68 A
267 W
199
505x850x1315
EFP7000/EFP9000
2.55 A
455 W
4.02 A
635 W
281
505x850x1315
* : For normal operating mode, without Booster nor Safety function activated.
In case of Booster function, add the standard primary concerned pump consumption (only if double pumps on
primary side).
In case of Safety function, add the standard primary pump consumption (only if double pumps on primary side)
and add the standard secondary pump consumption (only if double pumps on secondary side).
18.14 Current limiting fuses
Power cards are equipped with fuses, labelled FU1 to FU6 on the printed circuit.
Fuse
FU1
FU2
FU3
FU4
FU5
Protection
PUMP 1
PUMP 2
PUMP 3
PUMP 4
Power card
Size
6.3 x 32
6.3 x 32
6.3 x 32
6.3 x 32
6.3 x 32
Rating
2,5 A
2,5 A
2,5 A
2,5 A
250 mA
Voltage
250 V
250 V
250 V
250 V
250 V