Cetetherm AquaEfficiency
Installation, service and operating instruction
60
Unscrew the caps located at the opposite of primary and secondary ports.
Open top and bottom clips to
remove insulation.
To process cleaning, use CIP
connections 3/4" (CB60/FB52) or
1”1/2 (CB/FB76).
Remove the caps on the
connections and plug in the
cleaning system.
Cetetherm recommends the use of a pre-fitted Cetetherm CIP 20-type cleaning unit together with a specific
cleaning agent, such as AlfaPhos that is environmentally friendly.
There are several product solutions available depending on the cleaning job to be tackled. Use a neutralizing
solution, such as AlfaNeutra, before rinsing.
•
The circulator systems and pumps require no specific maintenance action.
Check annually that no leaks are detected level with the rotative seal when external motor pumps are
used.
Measure the electric motors consumption.
•
The control valves do not require any specific maintenance.
Annual check that no leaks are detected.
•
The control box does not requires any specific maintenance.
Annual check the electrical connection tightening.
18.3 Open the control box
Remove the front panel by turning the lock button counter clockwise and lift up
the cover.
Unscrew the two screws in bottom and lift up the panel.