C750 & C750R User
Manual Page 58
Transfer Time Line <-> Battery
0ms
Transfer Time INV<-> Bypass
0ms
Wafe form
Pure sine wave
Short Circuit Current on Normal Mode (3 phase
output)
30A for 10±1 cycle
74A for 10±1 cycle
Short Circuit Current on Normal Mode (1 phase
output)
90A for 10±1 cycle
222A for 10±1 cycle
Overload Capacity
105%-125% Load, 10 minutes transfer to Bypass;
125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass
BATTERY
Voltage
240VDC
480VDC
CHARGER
Charging Current (default)
2A
4A
2A
4A
Charging range
1~13A adjustable
OTHER MODE
CVCF
Yes (deterating to 60% load)
PHYSICAL
Dimension (WxDxH) mm
438 x 559 x 129(3U)
Net weight (Kg)
24
24
25
25
IP Protection Level
IP20
ENVIRONMENT
Operating Temperature
0-50
⁰
C (derating 50% above 40
⁰
C) excluding batteries
Relative Humidity
0-95% (non-condensing)
Operating Altitude
0-4000m (the load derating 1 % every up 100m @1000~3000m)
Storage temperature (with battery)
-15
⁰
C - 40
⁰
C
Storage temperature (without battery)
-25
⁰
C - 60
⁰
C
Certification
Safety
IEC/EN 62040-, UKCA, CE
EMC
IEC/EN 62040-2
Performance
IEC/EN 62040-3
(1)
In CVCF mode or dual source input mode, UPS needs to be de-rated to 60% capacity for 1-1 mode (rated output power and maximum
charging current).