C750 & C750R User
Manual Page 21
3.3.2 RACKMOUNTABLE MODEL
1.
This model support 2 installation modes: Rack installation and Tower installation.
2.
To keep good ventilation, please keep a free-space (500mm at least) for front / rear panels of the module.
3.
Do not carry the unit by the front or rear panels of the module during installation.
Rack installation
This procedure is suitable for 19 inches rack cabinet installation, it is recommended that the depth of the
cabinet be no less than 800mm.
UPS model
Identify the final position and keep ‘3U’ space for this installation.
1.
Install the rail kit (if configured). This rail kit is ‘2U
with screw holes (M5)’, the depth of the rail kit
is: 443-773mm.
2.
Fasten the rail kit to the cabinet with 8pcs M5
washers (as below)
3.
Install ‘Rack ear” to the unit by the M4 screws
(flat head).
4.
Slide the unit into the ‘rail kit’ and make sure to
tighten the ‘rack mounting screw’