C750 & C750R User
Manual Page 45
5.5 USER SETTINGS
JHD-APP version
Version of LCD driver
Communication card firmware
version
Version of IoT
Ethernet IP
IP address of ethernet
Ethernet MAC
MAC address of ethernet
WLAN IP
IP address of WLAN
WLAN MAC
MAC address of WLAN
Setting
Options on the display
Default
General
Audible Alarm
[Enabled], [Disabled]
Enabled
Date/Time
YYYY-MM-DD HH:MM
2020-1-1
Language
English, Italiano, Français, Deutsch, Español,
Русский
, Polski,
简
体中文
English
LCD brightness
[0%-100%]
100%
LCD saving mode
[Enabled], [Disabled]
Enabled
Screen rotation
[Auto Rotate], [Horizontal], [Vertical]
Auto Rotate
Input
Site wiring fault
(1)
[Enabled], [Disabled]
Disabled
Bypass voltage low limit
110 ~ (V_inverter - 15V)
187V
Bypass voltage high limit
(V_in 15V) ~ 276V
264V
Bypass frequency low
limit
-10%~-5%
-10%
Bypass frequency high
limit
5%~10%
10%
HE voltage low limit
-15%~-5%
10%
HE voltage high limit
5%~20%
10%
HE frequency low limit
-10%~-5%
5%
HE frequency high limit
5%~10%
5%
Dual input function
[Enabled], [Disabled]
Disabled
Output
UPS Mode
[Normal mode], [HE mode],
[CVCF mode]
Normal mode
Output voltage
[220V], [230V], [240V]
230V
Output frequency
[Auto detection], [50Hz], [60Hz]
Auto detection
ESS function
[Enabled], [Disabled]
Disabled
Auto bypass
[Enabled], [Disabled]
Enabled