Each boiler room
must be equipped with opening
for supply of fresh air which is dimensioned in
accordance with boiler output. Such opening must be protected with a net or grate. The boiler location
must never be under negative pressure.
Q - boiler output in kW
2
A - opening area in cm
A = 6,02 Q
Never cover the boiler or store debris or other materials near the
boiler, or in any way block the flow of adequate fresh air to the boiler.
Never cover the combustion air opening.
Insufficient combustion air for chimney vent boilers with room air for
combustion can lead to dangerous conditions.
Make sure that the combustion air supply and discharge openings
are not reduced or closed off.
Keep doors to the boiler room closed and do not block lovers in
boiler room door.
Protect the boiler room and avoid rodents and birds from entering
and blocking the air openings.
When the above issues have not been resolved, the boiler can not be
placed in operation.
Always follow the most up-to-date local, municipal and building
regulations and codes.
i
Boiler must not operate in flammable and explosive environment.
Equation for calculate opening area:
4.3. OPENING FOR FRESH AIR
2
Technical instructions
PelTec-Compact
12
Technical instructions
EKO-CKS P UNIT