HA2 Alarm Has Been Triggered
The cooling unit is designed to measure the temperature of the condenser coils and, if the
temperature exceeds 130°F, the HA2 alarm will display on the control panel.
If this alarm happens
when you first receive and start operating your CellarPro cooling unit
,
turn the fan to the “High” setting,
check for appropriate installation and ventilation on the Hot
Side of the cooling unit (Chapter II). Also,
make sure that there aren’t any obstructions to th
e
intake and/or exhaust vents.
If the cooling unit has been operating for several months without any problems and the alarm
occurs:
1.
Turn the fan switch to the “High” fan speed.
2.
There are 2 independent fans in the cooling unit. Make sure that the condenser fan (at
the rear of the cooling unit) is operating.
3.
Make sure that the filter (if used) or the coils are clean.
4.
Check for any blockages of the hot air intake or exhaust.
5.
If the cooling unit is a VSx (ie external) unit, the hood should be shaded.
If your unit continues to have issues,
turn off the cooling unit
and call CellarPro at 877.726.8496 or
.
LA2 Alarm has been triggered
As noted above, the cooling unit is designed to measure the temperature of the condenser coils
and, if the temperature drops below a certain point, the LA2 alarm will display on the control
panel. Please call CellarPro at 877.726.8496 if this alarm occurs.
Cooling Unit Won’t Turn On
The cooling system is programmed with a
3-Minute Delay
at Startup
to protect its internal
components.
Summary of Contents for 2000VSi
Page 1: ...V4 18 ControltheElements Owner sManual 2000VSi 2000VSx...
Page 2: ...V4 18 This page intentionally left blank...
Page 6: ...6 V4 18 2000VSi Cut Sheet...
Page 7: ...7 V4 18 2000VSi Cut Sheet As Ducted...
Page 8: ...8 V4 18 2000VSx Cut Sheet...
Page 15: ...15 V4 18 2000VSi Mounting Diagrams...
Page 16: ...16 V4 18 2000VSx Mounting Diagrams...
Page 23: ...23 V4 18...