Up and Down Buttons
To view the “
High Temp
” recorded by the cooling
unit,
press the “Up” button once.
To view the “
Low Temp
” recorded by the cooling
unit, press the “Down” button once.
To
reset
the “High Temp” or “Low Temp”, press
the “Set” button for three seconds while “Hi” or
“Lo” is displayed. “RST” will blink three times to
indicate confirmation.
Set Button
The cooling unit is factory preset with a Minimum
Set Point of 58°F and a Temperature Differential
of 4°F. This means that the cooling unit will turn
on when the display rises above 62°F (58°F + 4°F),
and turn off when the display falls below 58°F. In
this example, the average temperature inside the
cellar will be 60°F.
To v
iew the Minimum Set Point, press the “Set”
button for one second.
To change the Minimum Set Point,
•
Press the “Set” button for three seconds
until °F” blinks
•
Press “Up” or “Down” button
•
Press “Set” button to confirm
The “Set” temperature will blink three
times to
indicate confirmation
The recommended Minimum Set Point range is 53
- 60°F. To change the Temperature Differential,
see “Advanced Operation” later in this chapter.