Remote Control / Display Instructions
Digital Display
The temperature displayed on the control is red instead of blue.
Quick Chill
Button
Button
Icon
To activate the “Quick Chill” mode, press the “Up” button for three seconds
To deactivate “Quick Chill”, press the “Up” button for three seconds again
The “Quick Chill” indicator (Row
3) light will turn on when the cooling unit is in “Quick Chill”
mode,
In the “Quick Chill” mode, the cooling unit will
run continuously for 6 hours (or until the
unit reaches set point.). This mode is useful after loading “warm” bottles in the cabinet.
Auto Defrost
Mode
The cooling unit has a factory default defrost cycle that initiates every 16 hours for 20
minutes. When the cooling unit is in auto-
defrost mode, the “Defrost” Indicator light (Top
row) will turn on, and the evaporator fan will run.
Manual
Defrost
Hold the defrost button in for 3 seconds to initiate a manual defrost. The “Defrost”
Indicator light (Top row) will turn on for a 20 minute defrost cycle.
Light
The light button function is disabled, however pressing it will turn on/off the light indicator
on the display (2nd row).
Energy Saver
The remote display is not configured with an Energy Saver mode. The set point can be
raised manually for periods where energy savings is desired.
Summary of Contents for 2000VSi
Page 1: ...V4 18 ControltheElements Owner sManual 2000VSi 2000VSx...
Page 2: ...V4 18 This page intentionally left blank...
Page 6: ...6 V4 18 2000VSi Cut Sheet...
Page 7: ...7 V4 18 2000VSi Cut Sheet As Ducted...
Page 8: ...8 V4 18 2000VSx Cut Sheet...
Page 15: ...15 V4 18 2000VSi Mounting Diagrams...
Page 16: ...16 V4 18 2000VSx Mounting Diagrams...
Page 23: ...23 V4 18...