Monitoring Alarms
Text
ID
Name
Level
Def.
Map
Description/ Possible action
533
Test: system
alarm
Minor
/
A test will not start because there is an alarm that prevent
the battery test to start
534
Test: already in
boost
Minor
/
A test will not start because the battery is already in boost
charge.
535
Test: charger OFF
Minor
/
A test will not start because the charging is disabled and so
the battery will not be charged after the test.
Mappable Events (Not alarms !!)
Text
ID
Name
Level
Def. Map
Description
632
AC in failure
/
Major + R3
633
AC out 1 failure
/
Major
634
Battery 1 discharge
/
Major
635
Battery 2 discharge
/
Major
636
Battery 1 low
/
Major
637
Battery 2 low
/
Major
638
Digital input 1
/
Event
639
Digital input 2
/
Event
640
Digital input 3
/
Event
641
Digital input 4
/
Event
642
Digital input 5
/
Event
643
Digital input 6
/
Event
644
Digital input 7
/
Event
645
Digital input 8
/
Event
646
MBP Engaged
/
Major + R5
647
Battery bad
/
Minor
Means that a test has failed
648
AC out 1 overload
/
Major
649
AC out 1 redundancy lost
/
Event
650
AC in freq out of limit
/
Minor
651
Converter failure
/
Minor
652
Temperature sensor 1 fail
/
Minor
Battery probe
653
Temperature sensor 2 fail
/
Minor
Battery probe
654
Not used
/
Event
655
Module overtemperature
/
Minor
656
Surge arrester
/
Minor
657
AC out 1 redu1 lost
/
Event