![CE+T Power FLEXA 200 400/400 User Manual Download Page 65](http://html1.mh-extra.com/html/ce-t-power/flexa-200-400-400/flexa-200-400-400_user-manual_2577174065.webp)
Module DC input alarms
Text
ID
Name
Level
Def.
Map
Description
153
Source- no
voltage
Minor
DC- V is under input not present threshold
154
brownout
(<150V)
Minor
DC+ V is under extended lower limit for too much time
155
Source-
brownout
(<150V)
Minor
DC- V is under extended lower limit for too much time
156
Not defined 61
157
Not defined 62
158
Not defined 63
159
Not defined 64
Module AC input alarms
Text
ID
Name
Level
Def.
Map
Description
160
Start
Minor
161
Temperature
derating
Minor
Power is decreased due to high temperature
162
Temperature too
high
Minor
ACin converter stopped because of too high temperature
163
Temperature
sensor fail
Minor
Communication with temperature probe was lost
164
Auto-calib error
Minor
Error during auto-calibration of current offsets
165
Impedance Too
High
Minor
AC input too high impedance detected
166
Backfeed error
Minor
Input stopped because of backfeed on it
167
Not defined 72
168
Overcurrent
Minor
Too many consecutive ACin over-current trips
169
Driver not ready
Minor
Hardware driver not ready signal received
170
Driver fault
Minor
Hardware driver fault signal received
171
Driver perturbed
Minor
Too many consecutive “not ready”/”fault” from Acin driver
or more than a threshold over some hours
172
Not defined 77
173
Not defined 78
174
Not defined 79
175
Vres Absent
Minor
Fast alarm when source V is no longer present
65
– Flexa 200 - 400/400 – User Manual – v1.0
Summary of Contents for FLEXA 200 400/400
Page 17: ...17 Flexa 200 400 400 User Manual v1 0 Hardware setup Page 2...