5
cdvigroup.com
EN
ATRIUM A22POE
2-Door Controller
INSTALLATION MANUAL
EN
ATRIUM A22POE
2-Door Controller
INSTALLATION MANUAL
RECOMMENDED WIRING
SPECIFICATIONS
Equipment
Wire Type
Size
Maximum
Length
Card reader and
Wiegand keypad
4 to 8 conductors, stranded, shielded (foil), drain
conductor. For example: Alpha 5196, 5198, 5386,
5388, Belden 9553
22AWG (0.64mm) to
18AWG (1.02mm)
150m (500ft.)
Zone input
2 conductors, copper 22AWG (0.64mm)
22AWG (0.64mm)
600m (2000ft.)
Door strike
2 conductors, solid copper 18AWG (1.02mm)
18AWG (1.02mm)
150m (500ft.)
PoE+ (RJ-45)
CAT 5e 4 pairs UTP
100m (300ft)
Ethernet
CAT 5/5e
-
100m (300ft)
RS485 bus, Star or
Daisy Chain (no BIAS/
EOL required)
CAT 5/5e or 4 pairs
24AWG (0.51mm)
1220m (4000ft.)
4 conductors, copper
26AWG (0.40mm) to
18AWG (1.02 mm)
System Resources
Doors
2 (expandable to 10 doors)
Cards and users
Up to 10,000 cards and users
Schedules
Up to 250 Schedules each supporting up to 100 time periods (dd, hh:mm)
Buffered Events
Up to 25,000 events
Holidays
Up to 100 holidays (yyyy-mm-dd, hh:mm)
Access Levels
Up to 1000 access levels
Operating Temperature
-20°C to +70°C (-4°F to +158°F)
Humidity
0% to 85% (non condensing)
System Autonomy
Full Distributed Architecture (100% Off-line Operation)
Firmware
Online Upgradeable
PCB Dimensions
19.9cm (7.83”) x 12.38 cm (4.875”)
Cabinet Dimensions
29 cm (11.4”) high, 28 cm (11”) wide, 8 cm (3.15”) deep
Inputs
Readers
2 x Wiegand Readers with Multiple Protocol Support (Wiegand 26-bit, 30-bit & 44-bit),
Magnetic Stripe ABA Track 2
Keypads
2 x Wiegand Keypad with Multiple Protocol Support (Wiegand 8-bit & 26-bit)
Multi-Purpose Inputs
6 zone inputs (up to 12 using ZONE DOUBLER) with optional individual WIRE CUT &
WIRE SHORT supervision.
Box Tamper
Normally Closed (N.C.) contact