BOx TAMPER SWITCHES
Connecting the tamper switches allows the A22POE to detect when the cabinet door is opened and/or when the
cabinet is removed from the wall. To install the tamper switches, see “Installing the Tamper Switches”.
To use both switches:
1.
Connect one end of the supplied wire to the door tamper switch
terminal and the other end to the wall tamper switch terminal.
2.
Connect the other terminal of the door tamper switch to the “TMP” terminals using the
supplied wire.
3.
Connect the other terminal of the wall tamper switch to the “GND” terminals using the
supplied wire.
To use only one switch:
1.
Connect one terminal of the tamper switch to the “TMP” terminals using the supplied wire.
2.
Connect the other terminal of the same tamper switch to the “GND” terminals using the
supplied wire.
If you do not use the tamper switch, connect a wire between the “TMP” and “GND” terminals.
INPUTS/
OUTPUTS
RS485
LOCAL
BUS
BATTERY
(12V DC)
INPUT
POWER
SUPPLY
ETHERNET
LOCAL
BUS
STATUS
LOCK 1
SETTING
LOCK 2
SETTING
READERS
INPUTS
LOCKS
A22
2-Door Web-Based IP Module
DOOR 1
DOOR 1
DOOR 2
DOOR 2
DOOR 1
DOOR 2
D
ATA
1
Red LED 1
Green LED 1
Buzzer 1
D
ATA
0
+12V DC
D
ATA
1
Red LED 2
Green LED 2
Buzzer 2
D
ATA
0
+12V DC
Com. Relay 1
N.O. Relay 1
N.C. Relay 1
Lock output 1
Com. Relay 2
N.O. Relay 2
N.C. Relay 2
Lock output 2
Door Contact 1
REX 1
+12V DC
Door Contact 2
REX 2
+12V DC
Tamper Switch
+24V DC
-
+12V DC
-
+12V DC
A+
B-
Input 1
Input 2
Output 1
+12 V DC
Output 2
ETHERNET
24V DC INPUT
BATTERY
MODULE TYPE
SYSTEM STATUS
Metal Box
Door Tamper Switch
(N.C.)
Metal Box
Wall Tamper Switch
(N.C.)