TU RS485/ETH serie
CD Automation srl
31
4.18 RELEASE MODE
After the phases of development and Debug it is possible to proceed with
the “
Release
” modality, clicking on the “
Release
” button
(Fig.6.10-A)
.
In the Status bar the message “
Release Mode
”
(Fig.6.10 -B)
will be
visualized and in the Tool bar the commands relative to the operations of
Debug and Download will be disabled.
In the “
Release
” Modality, at the power-on, the Controller will be
automatically set in “Run” condition, loading in the RAM memory the
Program saved in the Internal Flash memory.
In this modality it is possible to read and write the Internal Registers.
4.19 INIT MODE
The “
INIT
” modality can be used in case of fortuitous loss of configuration
to set the Controller in the default condition in order to recover the desired
configuration. In this modality the value of the following parameters of the
controller will be automatically set independently of the configuration saved
in Eprom.
IP Address
Value assigned automatically from the network by
a DHCP server
Modbus Node
0x0Ah (10)
PORT 0 (Slave)
Baud-rate = 9600 bps
In this modality is not possible to execute the Program (Run) and the
Debug functions are disabled but it is allowed to download the Program, to
read and write the Internal Registers and the Gateway function is enabled.
IMPORTANT:
In “
Debug”
modality, at the power-on the Controller will be auto-
matically set in “Stop” condition without load and execute the Program. For
such reason, at the end of the Debug operations, set the Controller in “
Re-
lease”
modality.
In
“INIT”
modality is not possible to execute the Program (Run) and
the Debug functions are disabled but it is allowed to download the Pro-
gram, to read and write the Internal Registers and the Gateway function is
enabled.
Fig. 6.9
A
B
Fig. 6.10
B
A