TU RS485/ETH serie
CD Automation srl
16
4.11 TU-RS485/ETH ANL only
Function only in TU-RS485/ETH ANL model
4.11.1.1 Analogue Input measure
Contains the measures of the inputs programmed in the register %R34.
Description
Register
channel 0
%R26
channel 1
%R27
4.11.1.2 Analogue output values
Contain the value to set in Integer format for the two output currents.
Number for 4 mA: 4000; number for 20 mA = 20000
Description
Register
channel 0
%R32
channel 1
%R33
4.11.1.3 FREQ [x]
Contains the measure of each digital input's frequency.
The resolution is 0.01Hz.
Description
Register
channel 0
%R928
channel 1
%R929
4.11.1.4 COUNTER [x]
Contains the pulse counter (32 bit) each digital input.
Each counter is automatically incremented at each rise front of the relative digital input.
Description
Register
channel 0
%R932 + %R933
channel 1
%R934 + %R935