TU RS485/ETH serie
CD Automation srl
15
4.10.1.14
TIMERS Enable
Field of 1 read/write Register. Each bit of this Register is associated to an internal Timer. The Timer starts to
count when the associated bit is set as 0; when the parameter “ time” of the Timer Function Block set for the
Timer has passed, the Timer stops to count and the associated bit is automatically forced to 1.
4.10.1.15
RTC (Real Time Clock/Calendar)
Field of 4 read/write Registers: contain the value of the internal clock.
The following information are available:
Seconds
00 ÷ 59
Minutes
00 ÷ 59
Hours
00 ÷ 23
Day of week
01 ÷ 07 (01=Sunday, 02=Monday, .... 07=Saturday)
Date
01 ÷ 31 (it depends on the month)
Month
01 ÷ 12 (01=January, 02=February, .... 12=December)
Year
00 ÷ 99 (00=2000, 99=2099)
NOTE: all of the values are expressed as hexadecimal characters .
NOTICE! Writing these Registers will imply the variation of the clock and calendar settings.