CD Automation srl
STE Soft Starter
User’s Manual
41
P009 (H09)
::+
RMS Current on the phase R
A
R
Function:
This parameter read only shows the RMS current present on the power terminal
L1.
P010 (H0A)
::,
RMS Current on the phase S
A
R
Function:
This parameter read only shows the RMS current present on the power terminal
L2.
P011 (H0B)
::/
RMS Current on the phase T
A
R
Function:
This parameter read only shows the RMS current present on the power terminal
L3.
P013 (H0D)
"+:$
Line Frequency
Hz
R
Function:
This parameter read only shows the Frequency value of the power supply
P064 (H40)
=:=
Digital Input Display
R
Function:
This parameter read only shows the status of the digital input
Value:
00 = Digital Inputs not active
01 = Digital Input 1 (Stop) active
02 = Digital Input 2 (Start) active
10 = Digital Input 3 (Configurable) active
20 = Digital Input 4 (Configurable) active
Note:
If more Digital Inputs occur, the value will be equal at the sum of the two
Digital Inputs.
example: Digital Input 4 + Digital Input 2= 20 + 02 = 22
P065 (H41)
= :=
Digital Output Display
R
Function:
This parameter read only shows the status of the digital Output
Value:
00 = Digital Outputs not active
01 = Digital Output 1 active (not for size S9)
02 = Digital Output 2 active
10 = Digital Output 3 active
20 = Digital Output 4 active
Note:
If more Digital Outputs occur, the value will be equal at the sum of the two
Digital Outputs.
example: Digital Output 4 + Digital Output 2= 20 + 02 = 22
P066 (H42)
)$:=
Phase Sequence Display
R
Function:
This parameter read only shows the Phase Sequence status
Value:
0 = Phase Sequence OK
1 = Phase Sequence Wrong
P067 (H43)
3':=
Current Limit Display
R
Function:
This parameter read only shows the Current Limit status
Value:
0 = No Limit
1 = Current Limit active
P068 (H44)
*':=
Ramp low Display (zero speed)
R
Function:
This parameter read only shows the Ramp to zero status
Value:
0 = ramp active
1 = Ramp low (zero speed)
P069 (H45)
*$:=
Ramp up Display (at speed)
R
Function:
This parameter read only shows the Ramp up status
Value:
0 = ramp active
1 = at speed