CD Automation srl
STE Soft Starter
User’s Manual
42
9.2
Hardware Menu
P088 (H58)
=:
Digital input 3 configuration (terminal 19)
R/W
Function:
This parameter selects the function of digital input 3.
Value:
0 = Immediate Stop
1 = External Alarm
2 = Reset Alarm
Default: 1
P089 (H59)
=:
Digital input 4 configuration (terminal 20)
R/W
Function:
This parameter selects the function of digital input 4.
Value:
0 = Immediate Stop
1 = External Alarm
2 = Reset Alarm
Default: 2
P090 (H5A)
= :
Digital output 3 configuration (terminal 15)
R/W
Function:
This parameter selects the function of the digital output 3.
Value:
0 = Current Limit active
1 = Critical Alarm active
2 = Motor PTC Probe
3 = Thermal Overload
4 = Bypass active
Default: 1
P091 (H5B)
= :
Digital output 4 configuration (terminal 16)
R/W
Function:
This parameter selects the function of the digital output 4.
Value:
0 = Current Limit active
1 = Critical Alarm active
2 = Motor PTC Probe
3 = Thermal Overload
4 = Bypass active
Default: 4
P098 (H62)
3 CC
AC motor Connection Type
R/W
Function:
This parameter selects the type of the motor connection.
Value:
0=star (3wire)
1=delta (3wire)
2=Open delta (6wire)
Default:
0 (if not specified in the Order Code)
Note:
P099 (H63)
:#
Full scale of Analog Output 1
Kw-A
R/W
Function:
This parameter is used to adjust the full scale value of the analog output.
Min/Max:
0 ÷ 409.5 (for size 9 and 11)
0 ÷ 4095 (for size 13 and 14)
Default:
Nominal Current of STE Soft Starter (if not specified in the Order Code)
Note:
Use the parameter P101
:
to select the output configuration
P100 (H64)
(
Offset of the Analog Output
R/W
Function:
This parameter is used to set the offset for the Analog Output.
Value:
0 = 0 ÷ 10Vdc / 0 ÷ 20mA
1 = 4 ÷ 20mA
Default: 0
Summary of Contents for STE Series
Page 1: ...USER S MANUAL Rev 01 2007 STE Enhanced Soft Starter ...
Page 2: ......