CD Automation srl
STE Soft Starter
User’s Manual
40
9
Configuration Parameters
The Configuration Parameters are accessible from the Control Panel (place in front of unit), from the
software configurator or through the serial communication port RS485.
With the RS485 Serial Port the parameters are not divided by menu, but only by numerical order.
P000 (H00)
)--
Password
R/W
Function:
This parameter gives access at the available menus.
Value:
0 = Operator Menu
5 = Setup Menu
10 = Hardware Menu
Note:
With the RS485 Serial Port this parameter are not used.
9.1
Operator Menu
P001 (H01)
':
Code of Critical alarm group 1 (Soft Starter group)
R
Function:
This parameter read only gives information on the following alarms that they
stop the STE Soft Starter.
Valore:
00 = No Alarm
01 = Phase Loss
02 = Phase Inversion
04 = Undervoltage
10 = Overvoltage
20 = Thyristor Failure
40 = Heat-sink over temperature
Note:
If more alarms occur, the value will be equal at the sum of the two alarms.
example: Overv Phase Inversion = 10 + 02 = 12
P002 (H02)
':
Code of Critical alarm group 2 (Motor group)
R
Function:
This parameter read only gives information on the following alarms that they
stop the STE Soft Starter.
Value:
00 = No Alarm
01 = Thermal Overload
02 = Unbalance
04 = Start Failure
10 = External Alarm
Note:
If more alarms occur, the value will be equal at the sum of the two alarms.
example: External Alarm + Unbalance = 10 + 02 = 12
P004 (H04)
':=
Code of Not-Critical alarm
R
Function:
This parameter read only gives information on the following alarms that don't
stop the STE Soft Starter.
Value:
00 = No Alarm
01 = Motor PTC Probe
02 = Internal Error
Note:
If the parameter P038 (H26)=1 then Motor PTC Probe stop the STE Soft Starter
P006 (H06)
0:'C
Voltage supply
V
R
Function:
This parameter read only contains the voltage value of the power supply.
P008 (H08)
) 1/
Average power output
Kw
R
Function:
This parameter read only show the Average power output.