CD Automation srl
STE Soft Starter
User’s Manual
44
9.3
Setup Menu
P016 (H10)
@:0
Operative Voltage
V
R/W
Funzione:
This parameter is used to set the operative voltage
Min/Max:
24 ÷ 600
Default:
400 (if not specified in the Order Code)
P017 (H11)
"':
Full Load Current of AC motor (In)
A
R/W
Function:
This parameter is used to set the Full Load Current of AC motor (In)
Min/Max:
0 ÷ 409.5 Ampere (for size 9 and 11)
0 ÷ 4095 Ampere (for size 13 and 14)
Default:
Nominal Current of STE Soft Starter (if not specified in the Order Code)
Example:
Size of STE Soft Starter : 100A
Full Load Current of AC motor: P017
"':
=50.0 (50A)
Note:
This parameter is necessary to have the correct rescaling inside the unit. For
this reason it's very important specify this value in the order code.
P018 (H12)
3'
Current Limit value
%
R/W
Function:
This parameter contains the Current Limit value, set in % of FL_A
Min/Max:
150 ÷ 500%
Default: 300
P019 (H13)
3 ,"
Power Factor Cos
φ
R/W
Function:
This parameter contains the Power factor value
Min/Max:
0.10 ÷ 1.80
Default: 0.83
P020 (H14)
*@:1
Acceleration Ramp
Sec
R/W
Function:
This parameter is the rise time of the starter torque between 0 and the nominal
torque.
Min/Max:
0 ÷ 60 seconds
Default: 10
P021 (H15)
-//@
Start Type selection
R/W
Function:
This parameter selects the type of start ramp (voltage or current).
Value:
0 = Voltage ramp
1 = Current ramp
Default: 0
P022 (H16)
0:,/
Initial Voltage (Not used with Current ramp)
%
R/W
Function:
This parameter set in % the initial voltage value.
Min/Max:
0.0 ÷ 100.0%
Default: 30.0
Summary of Contents for STE Series
Page 1: ...USER S MANUAL Rev 01 2007 STE Enhanced Soft Starter ...
Page 2: ......