REVO S
3PH from 300A to 800A
User’s manual
13
Technical Specifications
3.1 General features
Cover and Socket material:
PolymericV2
Utilization Category
AC-51 AC-55b
IP Code (300-500A):
20
IP Code (800A):
00
Method of Connecting
Load in Delta, Load in Star
Auxiliary voltage:
Order code RS3_ _ _ -_1 = line voltage 100/120V voltage range 90:135V (8 VA Max)
Order code RS3_ _ _ -_2 = line voltage 200/208/220/230/240V voltage range 180:265V (8 VA Max)
Order code RS3_ _ _ -_3 = line voltage 277 voltage range 238:330V (8 VA Max)
Order code RS3_ _ _ -_5 = line voltage 380/400/415/440/480V voltage range 342:528V (8 VA Max)
Order code RS3_ _ _ -_6 = line voltage 600V voltage range 540:759V (8 VA Max)
Order code RS3_ _ _ -_7 = line voltage 690V voltage range 540:759V (8 VA Max)
Relay output for Heater Break Alarm:
0.5A a 125VAC
(only with HB option)
3.2 Input features
Analogic Input V:
0 ÷ 10Vdc impedance 15 kΩ
Analogic Input A:
4 ÷ 20mA impedance 100 Ω
Potentiometer:
10 kΩ min.
Digital Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
3Hz Max duty cycle min. 100 ms
3.3 Output features (power device)
Current
Nominal
Voltage
range (Ue)
Repetitive peak
reverse voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I
2
T
value
Suggested
A2s
(at 500V)
Frequency
range
Power loss
Thy
Fuse
Isolation
Voltage
(Ui)
(A)
(V)
(480V)
(600V)
(mAeff)
(10 msec.)
(A)
(mAeff)
tp=
10msec
(Hz)
I =Inom (W)
(A)
300
24÷600
1200
1600
300
5250
15
73500
47÷70
1324
2500
350
24÷600
1200
1600
200
7800
15
150500
47÷70
1439
2500
400
24÷600
1200
1600
200
8000
15
150500
47÷70
1641
2500
450
24÷600
1200
1600
1000
17800
15
294000
47÷70
2096
2500
500
24÷600
1200
1600
1000
17800
15
294000
47÷70
2096
2500
800
24÷600
1200
1600
1000
15000
15
246400
47÷70
2529
3422
3