REVO S
3PH from 300A to 800A
User’s manual
19
5.3 Cable dimensions (suggested) of Earth and of the Command Terminals
Current
Earth
Command Terminals
Cable
Screw
Cable
mm²
AWG
M
mm²
AWG
300A (S14)
50
1
M8
0,50
18
350A (S14)
50
1
M8
0,50
18
400A (S14)
50
1
M8
0,50
18
450A (S14)
70
1/0
M8
0,50
18
500A (S14)
70
1/0
M8
0,50
18
800A (S17)
70
1/0
M8
0,50
18