10.7 Soft Start
P240 - Soft-Start type Loop 1 (Address ModBus 2240)
P250 - Soft-Start type Loop 2 (Address ModBus 2250)
P260 - Soft-Start type Loop 3 (Address ModBus 2260)
Enables and selects the type of soft-start 1
0
1
2
Disab.
Grad.
Perc.
Disabled (
Default
)
Gradient
Percentage
P241 - Gradient Soft-Start Loop 1 (Address ModBus 2241)
P251 - Gradient Soft-Start Loop 2 (Address ModBus 2251)
P261 - Gradient Soft-Start Loop 3 (Address ModBus 2261)
Up/down gradient for soft-start
0 ÷ 20000 Digit/hour (degrees.tenth/hour if temperature).
Default:
100.0
P242 - Soft-Start 1 percentage (Address ModBus 2242)
P252 - Soft-Start 2 percentage (Address ModBus 2252)
P262 - Soft-Start 3 percentage (Address ModBus 2262)
Percentage of output during soft-start function 1
0 ÷ 100%.
Default:
50%
P243 - Soft-Start threshold Loop 1 (Address ModBus 2243)
P253 - Soft-Start threshold Loop 2 (Address ModBus 2253)
P263 - Soft-Start threshold Loop 3 (Address ModBus 2263)
Threshold below which the percentage soft-start function is activated, on power-up
-30000 ÷ 30000 [digit] (degrees.tenth/hour if temperature)
Default:
1000
P244 - Soft-Start time Loop 1 (Address ModBus 2244)
P254 - Soft-Start time Loop 2 (Address ModBus 2254)
P264 - Soft-Start time Loop 3 (Address ModBus 2264)
Maximum duration of soft-start 1: If the process does not reach the threshold entered in Par. "Soft-Start
Threshold" (P243-P253-P263) within the set time, the controller starts to adjust to the setpoint.
00:00 Disabled
00:01-24:00 hh:mm
Default:
00:15