Technical Specifications
5.1 General features
Cover and Socket material:
Polymeric V2
Utilization Category:
AC-51 AC-55b AC-56A
IP Code:
20
Method of Connecting:
Load in Delta, Load in Star
Auxiliary voltage:
24Vdc 1A
Relay output for Heater Break Alarm 0.5A a 24Vac/dc
(only with HB option)
5.2 Input and Output features (power device)
Current
Nominal
Voltage
range (Ue)
Repetitive peak
reverse voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I2T
value
Suggested
A2s
(at500V)
Frequency
range
Power loss
Thy
Fuse
Isolation
Voltage
(Ui)
(A)
(V)
(480V)
(600V)
(mAeff)
(10 msec.)
(A)
(mAeff)
tp=
10msec
(Hz)
I =Inom (W)
(Vac)
30
24÷600
1600
600
520
15
546
47÷70
36
3000
3000
50
24÷600
1600
600
1500
15
1750
47÷70
54
3000
3000
75
24÷600
1600
600
1900
15
4305
47÷70
102
3000
3000
90
24÷600
1600
600
1900
15
4305
47÷70
145
3000
3000
5.3 Input features (electronic control board)
configurable via software
Input n°: 3
Resolution 16Bit
Thermocouple
Type: K, S, R, J, T, E, N, B with automatic joint compensation
Tol/- 0,2% FS
Cold junction ac/- 0,1 °C/°C
V/mA
Type: 0-1V, 0-5V, 0-10V, 0-20mA, 4-20mA, 0-60mV
Impedence:
0-10 V: > 110 KΩ
0-20 mA: < 5 Ω
0-60 mV: > 1 MΩ
5.4 Output features (electronic control board)
Relay
Function: Cooling, temperature alarms, system alarms, system signals
DO 1,2,3: 230Vac / 1A resistive load
AL4: 230Vac / 1A resistive load
AL5: 24V / 1A