REVO RT
from 35A to 90A
User’s manual
45
P164 - Input selection Alarm 1 (Address ModBus 2164)
P178 - Input selection Alarm 2 (Address ModBus 2178)
P192 - Input selection Alarm 3 (Address ModBus 2192)
Selects the input connected to the alarm
0
1
2
Input 1. (
Default
for Alarm1)
Input 2. (
Default
for Alarm2)
Input 3. (
Default
for Alarm3)
Alarm 4, Alarm 5 not available
P165 - Reference SP selection for Alarm 1 (Address ModBus 2165)
P179 - Reference SP selection for Alarm 2 (Address ModBus 2179)
P193 - Reference SP selection for Alarm 3 (Address ModBus 2193)
Select reference Loop
0
1
2
SP 1. (
Default
for Alarm1)
SP 2. (
Default
for Alarm2)
SP 3. (
Default
for Alarm3)
Alarm 4 not available
P166 - Alarm 1 State Output (Address ModBus 2166)
P180 - Alarm 2 State Output (Address ModBus 2180)
P194 - Alarm 3 State Output (Address ModBus 2194)
P208 - Alarm 4 State Output (Address ModBus 2208)
Alarm 1 output contact type and intervention type
0
1
2
3
4
5
(N.O. Start) normally open, operational from start (
Default
)
(N.C. Start) normally closed, operational from start
(N.O. Threshold) operational when the alarm is reached
(N.C. Threshold) operational when the alarm is reached
(N.C. Threshold Variation) inhibited after command set change
(N.C. Threshold Variation) inhibited after command set change
P167 - Hysteresis Alarm 1 (Address ModBus 2167)
P181 - Hysteresis Alarm 2 (Address ModBus 2181)
P195 - Hysteresis Alarm 2 (Address ModBus 2195)
P209 - Hysteresis Alarm 4 (Address ModBus 2209)
Hysteresis alarme
-10000 ÷ +10000 [digit] (degrees.tenths for temperature sensors).
Default:
0.5.
P168 - Reset Alarm 1 (Address ModBus 2168)
P182 - Reset Alarm 2 (Address ModBus 2182)
P196 - Reset Alarm 3 (Address ModBus 2196)
P210 - Reset Alarm 4 (Address ModBus 2210)
Alarm contact reset type
0
1
2
3
Automatic reset (
Default
)
Manual reset (manual reset form keyboard or digital input)
Manual reset stored (maintains the output status even after any power failure)
Automatic reset with time activation. The alarm remains active for the time set in the "Alarm delay" parameter P171, P185,
P199, P213, even if the conditions that generated it are no longer present. The alarm conditions must be cleared before
it can be triggered again.