REVEX
1PH 280A
User’s manual
29
9.4.2 Setup Menu
This section describes each item on the setup menu. Use this menu to configure the power controller for the
load.
The password to access this menu is 2.
Parameter Name
Description
Range
Unit
Modbus
Address
Par.
Type
Out Scale
Set the percentage by which the set point
is scaled. For example, if a 0 to 10V analog
input providing the set point is 5V and output
scaling is 80% then the effective set point is
40%
0 to 100.0
%
16
Read
Write
100
80
60
40
20
0
0 20 40 60 80 100
Input
Output Scaling = 100%
Output Scaling = 80%
Output Scaling = 40%
Scaled Set P
oint
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
I Limit SP
Set the maximum percent of the
nominal current that the power control
allows. This parameter indicates RMS
current by default.
When parameter 52 is set to 1, this
parameter indicates peak current
100%
0 to 100.0
%
17
Read
Write
Nom Line V
Set the nominal value for the line
voltage input
220V
0 to 1023
V
37
Read
Write
Nominal I
Set the nominal load current
Maximum
current
0 to 999.9
A
38
Read
Write
Soft Start
Set the duration of the soft start in
increment of 100mSec. The power
controller ramps set to point changes
over the time set here. For more
information see “Firing type” page:
Soft Start with Burst Firing and Soft
Start with Phase Angle
100
(10 sec)
0 to 255
(0 to 25,5
sec)
23
Read
Write
SP select
Choose the source for the remote
set point
0
61
Read
Write
Option
Value
Analog In 1
0
Analog In 2
1
Summary of Contents for REVEX 1Ph 280A
Page 2: ......