28
REVEX
1PH 280A
User’s manual
9.4.1 Operator Menu
This section describes each item on the operator menu. Use this menu to view the measured values and basic
settings of the power controller.
The password to access this menu is 0.
Parameter Name
Description
Range
Unit
Modbus
Address
Par.
Type
Set Point
View the set point
0 to 100
%
15
Read
Only
Volts Out
Indicates the average (RMS) voltage of all
phases
0 to 1023
V
10
Read
Only
Current
Indicates the average (RMS) current of all
phases
0 to 1023
V
11
Read
Only
Power
Indicates the average (RMS) power output
0 to 100
%
12
Read
Only
Volts In
Indicates the average (RMS) voltage input
0 to 65535
V
47
Read
Only
Frequency
Indicates frequency of the power input
0 to 655.35
Hz
9
Read
Only
Pwr Factor
Indicates power factor of the output power
0 to 1000
102
Read
Only
Load Ω
Indicates the resistance of the load
0 to 655.35
Ω
46
Read
Only
I Limit SP
Indicates the maximum percent of the nominal
current that the power control allows. This
parameter indicates RMS current by default.
When parameter 52 is set to 1, this parameter
indicates peak current
0 to 100
%
17
Read
Only
Out Scale
Indicates the percentage by which the power
demand set point is scaled
0 to 100.0
%
16
Read
Only
Nom Line V
Indicates the user-set, nominal value for the
line voltage input
0 to 1023
V
37
Read
Only
Nominal I
Indicates the user-set, nominal load current
0 to 999.9
A
38
Read
Only
Summary of Contents for REVEX 1Ph 280A
Page 2: ......