CANplus CP1000
Control Panel Operation Manual
*Patent Pending
40
9M02-1000-A401-EN Revision G
11 Miscellaneous
11.1 Emissions System Functionality
Note:
GENERAL EMISSIONS DISCLAIMER This panel may include provision(s) for operator input such as FORCE
REGENERATION, INHIBIT REGENERATION, INTERLOCK, and others specific to US and International
emissions regulations. Responsibility for emissions-related inputs and compliance with emissions regulations is
solely that of the owner and/or operator of the machine/engine or motor on which this panel is connected.
CAUTION
CAREFULLY READ AND UNDERSTAND THE ENGINE MANUFACTURER OWNER/OPERATOR
MANUAL. YOUR ENGINE MANUFACTURER PROVIDES SPECIFIC INFORMATION REGARDING
THE EXHAUST EMISSION SYSTEM OF YOUR ENGINE. THIS INFORMATION IS MAINTENANCE,
PROCEDURAL AND SAFETY RELATED. FAILURE TO EXACTLY FOLLOW THE ENGINE
MANUFACTURER INSTRUCTIONS AND SCHEDULES COULD POTENTIALLY RESULT IN HARM
OR INJURY TO YOU AND/OR OTHERS. FURTHER, FAILURE TO EXACTLY FOLLOW THE
ENGINE MANUFACTURER INSTRUCTIONS AND SCHEDULES COULD RESULT IN DAMAGE TO
YOUR ENGINE AND/OR EQUIPMENT.
The CANplus display reports emissions messages received from the engine ECU. Depending on the received
message, icons or symbols may be displayed on the screen. Some messages/icons are displayed as an overlay
(inhibit symbol shown at left). Other symbols/icons may cover most of the screen. The operator MUST respond
to the indications on the display following engine manufacturer recommended procedures/actions. Please note
that indications shown by the display may vary with respect to engine manufacturer and may vary between
engine models from the same manufacturer.
11.2 CP1000 Panel Wiring
Most electronically governed engine installations include a harness with a built-in J1939 backbone. Use twisted
shielded pair with a drain wire for CAN wiring terminated with 120
Ω resistors at each end. The maximum length
for the CAN bus is 131 ft (40 m) and stubs should not exceed 39 in (1 m) in length.
!