6.4.1 Configuring Operation
Configuring Autostart begins with selecting the desired behavior. The two choices are as follows:
1.
High to low, examples:
•
High water level to low water level
•
High pressure to low pressure
•
High temperature to low temperature
2.
Low to high, examples:
•
Low water level to high water level
•
Low pressure to high pressure
•
Low temperature to high temperature
6.4.2 Configuring Start and Stop Events
The next step is to define the start and stop events. The choices are as follows:
•
Single switch
•
Cycle Run
–
Start upon entering Autostart modes
–
Stops after x minutes
–
Restarts after y minutes
•
2-State, Single Switch
–
Manually started and stopped
–
Switched input toggles between idle (open) and Intermediate RPM (closed)
•
Remote Control
–
Start and stop via switch
–
Throttle up and down via two other switches
–
Single start/stop
•
Dual switch
–
Start and stop via dual (high and low) switches
•
Transducer
–
Start and stop via transducer level
•
Transducer with backup switches
–
Start and stop via transducer level
–
Switches as backup start and stop if there is a transducer failure
•
Scheduler
•
Timed run
–
Manually started
–
Automatically stopped by countdown timer
–
Can maintain a level while running
The following table describes the Start/Stop events when behavior operation is set to “High to Low”
(switches/floats are normally open):
Start/Stop Events
Engine or Motor Starts When
Engine or Motor Stops When
Single Switch
SW1 is closed
SW1 is open
Dual Switch
SW1 and SW2 are both closed
SW1 and SW2 are both open
Transducer
Input is above high set point
Input is below low set point