T-366
tESt - Sensor Tests
During a sensor test, the controller will verify that the CO
2
sensor is reading 0% and the O
2
sensor is in a
valid range. If both meet this requirement, a calibration test “CAL StArt” will be displayed for five seconds,
a CO
2
sensor calibration will be performed and an O
2
sensor validity check will be performed. Then, a ten
minute countdown timer is placed in the right hand display.
If both sensors pass, a “CAL PASS” message will display for five minutes or until the user presses and
holds the CODE SELECT key for five seconds. In either case, normal operation will be resumed.
If one or both of the sensors are outside of the range, check condition requirements. The failed results will
be displayed “No CAL”, alternating every five seconds. To exit, the user should press and hold the CODE
SELECT key for three seconds. A “CO
2
FAIL” or “O
2
FAIL” message will appear if the test fails.
If the range check fails (indicating a drifted sensor), verify that the box is clean of cargo remnants from last
trip, open the back doors, and rerun the test. If the range check fails a second time, replace the sensor that
is out of range.
If either of the sensors fail open or shorted, an Alarm 09 for O
2
sensor or Alarm 10 for CO
2
sensor will occur.
NOTICE
It is required that the calibration procedure only be performed during pre-trip or when the con-
tainer has been fully vented.
4.6
CODE 44 (CD44)
4.6.1
Display Cd44 Values
1. Press the CODE SELECT key on the keypad.
2. Press the UP or DOWN arrow keys until “Cd44” is in the left display, then press ENTER.
3. Press the DOWN arrow key to toggle between the different values available in this sub menu.
Cd44 allows the user to view the following XtendFRESH values: CO
2
setpoint, CO
2
per-
centage, O
2
setpoint, O
2
percentage, and O
2
voltage.
For the CO
2
setpoint, the range is from 0 to 19% in 1% increments with a default setting
of 5%. For the O
2
setpoint, the range is from 3% to 21% in 1% increments with a default
setting of 10%.
CO
2
Setpoint
CO
2
%
O
2
Setpoint
O
2
%
O
2
Voltage
Summary of Contents for XtendFRESH
Page 2: ......
Page 4: ......
Page 8: ...T 366 iv LIST OF TABLES TABLE NUMBER Page Table 6 1 Maintenance Schedule 6 1...
Page 12: ......
Page 42: ...T 366 7 2 Figure 7 1 PIDs NT2570 and NT2617 Schematic and Diagram...
Page 43: ...7 3 T 366 Figure 7 2 PIDs NT2570 and NT2617 Schematic and Diagram Page 2...
Page 44: ...T 366 7 4 Figure 7 3 PIDs NT2570 and NT2617 Diagram and Legend...
Page 45: ...7 5 T 366 Figure 7 4 PIDs NT2619 and NT2704 Schematic and Wiring Diagram...
Page 46: ...T 366 7 6 Figure 7 5 PIDs NT2619 and NT2704 Schematic and Wiring Diagram Page 2...
Page 47: ...7 7 T 366 Figure 7 6 PIDs NT2619 and NT2704 Diagram and Legend...
Page 48: ...Figure 7 7 PIDs NT2709 and NT2774 Schematic and Wiring Diagram...
Page 49: ...7 9 T 366 Figure 7 8 PIDs NT2709 and NT2774 Schematic and Wiring Diagram Page 2...
Page 50: ...T 366 7 10 Figure 7 9 PIDs NT2709 and NT2774 Diagram and Legend...
Page 52: ...T 366 9 1 9 Parts List for XtendFRESH Sheet 1 of 2 6 7 9 12 2 8 10 15 3 5 1 10 11 4 5 14...
Page 68: ......
Page 71: ......