background image

T-366

5–2

AL10

CO

2

 SENSOR FAILURE

Cause:

Triggered anytime the CO

2

 sensor reading is outside of the normal operation range, after an initial

signal was detected

.

Component

CO

2

 Sensor

Troubleshooting

Check the voltage at MC5 to the ground pin on TP9. (1 - 4.7 vdc)
Check wiring (refer to schematic), and correct if found mis-wired.
If part is available, remove upper fresh air panel and evaporator motor; re-
place sensor. If no part is available, take no action and service at next PTI.
XtendFRESH will continuously run the scrubber. O

2

 level will be controlled

with the opening and closing of the fresh air vents as required.

AL29

LOSS OF ATMOSPHERIC CONTROL

Cause:

Triggered whenever the CO

2

 level is above its upper limit by 1% for 60 minutes. Or, when the O

2

level is greater than 1% below its setpoint for longer than 30 minutes after the unit has been in
range. The alarm is triggered off when the levels return to within the normal range.

Setup

Run Cd43 test mode for troubleshooting the below components. If test mode
times out, you must restart the mode prior to the continuation of testing.

Troubleshooting

If components do not energize, check FX1 and FX2 for power (460 VAC).
If fuse is open, check heater continuity (XHT1 to ground). Must be greater
than 1 mega ohm. If less than 1, disconnect the heater at XHT1 and XHT2.
Replace fuse. Unit will control on fresh air solenoids.

Component

Solenoid Air Vents. 

Troubleshooting

Visually inspect to see if the Solenoid Valves are opening air vents. If vents
open, troubleshoot the next component. If vents do not open, continue with
troubleshooting below.
Check FX4 fuse for power (~20 volts dc).
If fuse is open, check wiring and or replace solenoid if part is available.
If no part is available, open manual fresh air vent.

Component

XtendFRESH Fan(s) / XtendFRESH Scrubber Motor

Troubleshooting

Visually inspect to see if the XtendFRESH Fan(s) are running (air blowing on
left, intake on right), check current draw of motor at the XST1 (~40 to 200
milliamps / contactor load side). Troubleshoot the non-operating component.
If both are running, proceed to next component.
Verify XS contactor is pulling in. If not, check FX6 fuse for power (24 VAC).
If not, check power at controller KB4.
Check FX3 fuse for power (~20 vdc). If no power, replace fuse. If fuse opens
a  second  time,  take  no  further  action.  O

2

  level  will  be  controlled  with  the

opening and closing of the fresh air vents.
If part is available, replace either fan or scrubber motor. Fan is replaceable
from the front on a loaded unit; Scrubber motor is not. If no part is available
or accessible, take no action and service at next PTI. O

2

 level will be con-

trolled with the opening and closing of the fresh air vents.

Component

Heater

Troubleshooting

Verify XH contactor is pulling in. If not, check FX6 for power (24 VAC). If
open ohm contactors XHA1 and XSA1 to ground. Replace (12 Amp) con-
tactor. If contactor is pulling, power unit off and check heater resistance
from XH1 to XH2 (450 to 500 ohms). If heater is outside of the range, dis-
connect heater at XHT1 and XHT2 and replace at next PTI. Unit will control
on fresh air solenoids.

Summary of Contents for XtendFRESH

Page 1: ...Container Refrigeration OPERATIONS SERVICE AND PARTS MANUAL For XtendFRESHTM Controlled Atmosphere Option T 366 Rev G...

Page 2: ......

Page 3: ...OPERATIONS SERVICE AND PARTS MANUAL For Carrier Corporation 2018 Printed in U S A September 2018 XtendFRESHTM Controlled Atmosphere Option...

Page 4: ......

Page 5: ...e Active 4 2 4 5 3 Make Test Mode Active 4 2 4 6 CODE 44 CD44 4 3 4 6 1 Display Cd44 Values 4 3 4 7 CONTAINER VENTING PROCEDURE 4 4 TROUBLESHOOTING 5 1 5 1 ALARMS 5 1 5 2 XTENDFRESH ASSEMBLY NOT OPERA...

Page 6: ...S Switch 6 12 6 10 PRE TRIP 6 12 6 11 CONTAINER PREPARATION 6 13 6 11 1 Box Checkout Leak Test 6 13 6 12 CONTAINER CURTAIN 6 15 6 12 1 Installing the Curtain 6 16 ELECTRICAL WIRING SCHEMATIC AND DIAGR...

Page 7: ...e 6 15 Bolt Spring Assembly Dimension 6 10 Figure 6 16 Scrubber Housing 6 11 Figure 6 17 Scrubber Mounting Plate 6 11 Figure 6 18 Motor and Mounting Plate 6 12 Figure 6 19 Warning Label 6 13 Figure 6...

Page 8: ...T 366 iv LIST OF TABLES TABLE NUMBER Page Table 6 1 Maintenance Schedule 6 1...

Page 9: ...installation of XtendFRESHTM Controlled Atmosphere option Tag circuit breaker and power supply to prevent accidental energizing of circuit Do not bypass any electrical safety devices e g bridging an...

Page 10: ...he container ventilate before entering Stay away from doors while venting Refer to Section 4 7 WARNING Before servicing the unit make sure the Start Stop switch ST is in the OFF position Unit cir cuit...

Page 11: ...nd Service Parts Manual for the model of your particular refrigeration unit Carrier Transicold s exclusive XtendFRESH option is a modular system The XtendFRESH system s ability to con trol container a...

Page 12: ......

Page 13: ...on This panel may be removed to allow entry into the evaporator section where the CO2 scrubber and other components are located Figure 3 1 Refrigeration Unit Front 3 1 2 Evaporator Section Components...

Page 14: ...Assembly 2 Desorb Out Hose 3 CO2 Scrubber Motor 4 O2 Sensor 5 Fresh Air Solenoid 6 CO2 Sensor 7 Sensor Air Filter 8 O2 Amplifier 9 Desorb In Hose 10 O2 CO2 Inlet 11 O2 CO2 Outlet 12 Port Cap 2 1 5 9 6...

Page 15: ...low the lower setpoint NOTICE While the XtendFRESH option is operating the process of inducing ripening by introducing ethylene should not be performed 4 3 PRE TRIP INSPECTION Pre trip testing of the...

Page 16: ...CODE SELECT key on the keypad 2 Press the UP or DOWN arrow key until Cd43 is displayed 3 Press the ENTER key The selection in the right display will blink 4 Press the UP or DOWN arrow key until OFF mo...

Page 17: ...f the range check fails indicating a drifted sensor verify that the box is clean of cargo remnants from last trip open the back doors and rerun the test If the range check fails a second time replace...

Page 18: ...Cd43 select Fresh mode and set the operating parameters to 21 O2 Refer to Section 4 5 1 4 Allow the refrigeration unit to run This allows the evaporator fans to exchange low oxygen level air with amb...

Page 19: ...defective VPS If unit is loaded ensure vent is closed Note and replace VPS on next PTI The alarm will not affect the XtendFRESH system from operating AL09 O2 SENSOR FAILURE Cause Triggered anytime th...

Page 20: ...enoid Valves are opening air vents If vents open troubleshoot the next component If vents do not open continue with troubleshooting below Check FX4 fuse for power 20 volts dc If fuse is open check wir...

Page 21: ...back from the Scrubber Motor to the controller is not sensed when the motor is turning Component Scrubber Fuse Troubleshooting Check to see if Scrubber Fuse is blown Replace Fuse if necessary Componen...

Page 22: ...e Operation Normal Vents Open Check Fuse FX4 in XF Control Box Fuse is OK Check wiring for short replace fuse Check wiring connections to reefer controller FX5 FX6 in main control box Repair wiring or...

Page 23: ...e is OK Check wiring for short replace fuse Repair wiring and connections Does the XS contactor energize Wiring Connections to Fan s or Motor OK Replace Fan s or Motor Yes Yes Yes Yes No No No No Chec...

Page 24: ...olts to Heaters Yes Repair wiring from Main Control Box to XHL1 and XHL2 Fuses Are OK Check Fuses FX5 and FX6 in Reefer Control Box Cd43 run Test Mode Open XtendFRESH Control Box Check current draw fr...

Page 25: ...ommended 6 1 MAINTENANCE SCHEDULE 6 2 PANEL AIR FILTER 6 2 1 Removing the Panel Air Filter s 1 Remove the louvered panels from the right hand side refrigeration evaporator access panel Figure 6 1 by r...

Page 26: ...ure 6 2 Figure 6 2 Panel Air Filter s 6 2 2 Replacing the Panel Air Filter s 1 Install the panel air filter by reversing the above steps Be sure the filter is fully inserted until it hits the stop Als...

Page 27: ...ned OFF and tagged to prevent accidental energizing of circuits 6 3 1 Removing the Sensor Air Filter Element When replacing the Sensor Air Filter element it can be accessed in two ways through the lef...

Page 28: ...upper evaporator panel Figure 6 4 Refer to Section 6 6 for procedures to remove and install the left access panel WARNING Potential hazardous atmosphere and low oxygen levels inside the container ven...

Page 29: ...ow oxygen levels inside the container ventilate before entering Stay away from doors while venting Refer to Section 4 7 WARNING Before servicing unit make sure the start stop switch ST is in the OFF p...

Page 30: ...ht access panel Figure 6 1 by removing the mounting bolts and T I R locking device if used 2 Remove the eight 10 32 nuts holding the ducts in place Leave the blower fan mounted to its duct Gently push...

Page 31: ...H Fan s 1 Remove the two louvered panels from the upper right access panel Figure 6 1 by removing the mounting bolts and T I R locking device if used 2 Unbolt the defective fan from the panel Unplug t...

Page 32: ...urn the scrubber housing 10 degrees to remove it from the unit Figure 6 11 NOTE Original XtendFRESH units have a tall exhaust port and port cap Figure 3 2 and need to be removed in order to remove the...

Page 33: ...and aluminum seal plate Figure 6 13 Figure 6 13 Scrubber Separated with Filter 9 Install the seal plates and gaskets Replace if damaged Reinstall the new filter making sure the gasket and seal plate a...

Page 34: ...n the bottom of the washer and the housing tab surface Figure 6 15 Figure 6 15 Bolt Spring Assembly Dimension 6 7 2 Installing the Scrubber 1 Align the scrubber shaft in the slot of the coupling attac...

Page 35: ...cing the Scrubber motor it can be accessed through the inside of the container Refer to Figure 6 10 for the physical location of the motor 1 Start by removing the scrubber housing Refer to Section 6 7...

Page 36: ...d43 set to FrESH the signal provided to the controller will be sent from the Oxygen sensor If Cd43 is set to OFF the signal to the controller will be sent from the Vent Position Sensor VPS 6 9 1 Check...

Page 37: ...10 Load cargo install the new curtain and select the desired O2 and CO2 levels via Code Select Cd43 FrESh modes Refer to Section 4 5 1 11 Immediately after the cargo is loaded it is recommended to per...

Page 38: ...in can result in a failure of the test After connecting the gauges turn on the air supply and regulate the air pressure to 40 60 psi When the Magnehelic gauge reads 2 5 inches of water gauge shut off...

Page 39: ...ors Remove an install new curtain De pressurize the container prior to opening the con tainer Ensure manual fresh air panel is equipped with collars Part 79 04064 00 Figure 6 22 Fresh Air Panel Collar...

Page 40: ...curtain 3 Fully unfold the door curtain package and hold it up to the container opening Tape maybe be used to assist holding the curtain in position 4 Place curtain around door and seal curtain along...

Page 41: ...ion contains the Electrical Schematics and Wiring Diagrams for a basic unit with XtendFRESHTM Con trolled Atmosphere option Refer to the Operation and Service manual for your particular unit for actua...

Page 42: ...T 366 7 2 Figure 7 1 PIDs NT2570 and NT2617 Schematic and Diagram...

Page 43: ...7 3 T 366 Figure 7 2 PIDs NT2570 and NT2617 Schematic and Diagram Page 2...

Page 44: ...T 366 7 4 Figure 7 3 PIDs NT2570 and NT2617 Diagram and Legend...

Page 45: ...7 5 T 366 Figure 7 4 PIDs NT2619 and NT2704 Schematic and Wiring Diagram...

Page 46: ...T 366 7 6 Figure 7 5 PIDs NT2619 and NT2704 Schematic and Wiring Diagram Page 2...

Page 47: ...7 7 T 366 Figure 7 6 PIDs NT2619 and NT2704 Diagram and Legend...

Page 48: ...Figure 7 7 PIDs NT2709 and NT2774 Schematic and Wiring Diagram...

Page 49: ...7 9 T 366 Figure 7 8 PIDs NT2709 and NT2774 Schematic and Wiring Diagram Page 2...

Page 50: ...T 366 7 10 Figure 7 9 PIDs NT2709 and NT2774 Diagram and Legend...

Page 51: ...placement Components Group TR 20 P O Box 4805 Syracuse New York 13221 or FAX to 315 432 3778 8 2 LETTER DESIGNATIONS The following letter designations are used to classify parts throughout this list A...

Page 52: ...T 366 9 1 9 Parts List for XtendFRESH Sheet 1 of 2 6 7 9 12 2 8 10 15 3 5 1 10 11 4 5 14...

Page 53: ...er Plain 10 Type A 6 8 66 U 1 5321 7 Screw Cap Hexhead 1 4 20 x 1 4 9 66 U 1 5371 6 Screw Machine Hexhead 10 24 x 750 Slotted 6 10 66 U 1 5321 7 Washer Plain 1 4 W Type A 12 11 66 U 1 5361 47 Bolt Mac...

Page 54: ...T 366 10 1 10 Parts List for Panel Assemblies Sheet 1 of 2 XtendFRESH Panel Fresh Air Panel 79 04043 4 7 8 1 13 3 7 8 2 7 8 5 14 15 16 17 18 19 20 21 22 23 24 6 9 10 12 11...

Page 55: ...10 34 01146 04 Washer Lock M4 Spring 8 11 42 00823 00 Gasket 26 x 5 Half Round 1 12 34 01197 45 Screw Hexhead M4 0 7 x 45 8 13 62 11762 00 Label XtendFRESH Logo 1 14 79 04037 00 Filter Assembly inclu...

Page 56: ...T 366 10 3 10 Parts List for Panel Assemblies NT2617 and up Sheet 1 of 2 79 04086 XtendFRESH Panel Fresh Air Panel 14 3 7 8 1 4 7 8 12 22 21 5 6 9 10 13 15 16 17 18 19 20 23 24 25 2 7 8 26 11...

Page 57: ...11 34 66682 00 Washer Rubber 8 12 42 00237 00 Gasket 26 x 5 Half Round 1 13 34 01197 45 Screw Hexhead M4 0 7 x 45 4 14 62 11762 00 Label XtendFRESH Logo 1 15 79 04037 00 Filter Assembly includes 1 16...

Page 58: ...T 366 11 1 11 Parts List for Sensor Assembly Sheet 1 of 2 79 04035 17 18 19 20 2 12 14 17 11 13 15 16 10 9 17 5 9 17 21 17 20 1 3 4 26 3 16 5 6 7 8 21 24 23 22 25...

Page 59: ...1 Sensor Carbon Dioxide 1 13 10 00344 01 Sensor Oxygen 1 14 34 00373 61 Tube Clamp 88 Diameter Cushion 2 15 48 00297 00 Housing O2 Sensor 1 16 KA 70PP 048 Fitting Hose Inside Diameter BARB x NPT 3 17...

Page 60: ...T 366 12 1 12 Parts List for Scrubber Assembly Sheet 1 of 2 79 04044 4 2 7 8 10 7 8 10 7 8 10 3 8 9 1 5 8 9 6...

Page 61: ...2 58 04996 00 Gasket Seal 2 48 00504 00 Gauge 1 4 79 04029 00 Shaft Assembly 1 5 24 02028 02 Heater 230VAC 2 6 34 06386 00 Screw Cap Hex Head HD 2 7 34 06099 22 Screw cap sch 5 16 18 x 1 75 4 8 66 U...

Page 62: ...13 1 13 Parts List for Wiring Assembly Sheet 1 of 3 91 00440 5 6 24 9 28 10 4 23 29 22 2 4 4 23 10 27 28 32 8 1 7 17 32 15 16 12 13 14 18 19 33 37 36 6 33 34 35 39 38 21 18 19 31 2 4 26 3 11 20 30 2...

Page 63: ...2 01997 13 Seal AMP Wire Seal 9 CIRC 1 17 66SC0603AA0090 Spiral Conduit 3 4 inch x 9 00 Long 2 18 AT 39JA 171 Nut Hex 1 4 20 7 19 AU 27JR 171 Washer Lock External Tooth 7 20 66 U 1 9592 13 Standoff 1...

Page 64: ...00665 09 Nut Hex 10 32 1 37 AU 27JR 131 Washer Lock 10 External Tooth 1 38 62 03957 04 Decal Warning High Voltage 1 39 42 00776 00 Gasket 40 22 00060 36 Fuse 15 Amp Slow Blow Not Shown 2 41 76 66652 0...

Page 65: ...Plate 1 4 34 00662 09 Washer Plain 10 Medium 032 Thick 4 5 34 60000 20 Screw Machine Hexhead M5 x 20mm 787 4 6 58 05010 00 Cap End Motor 1 7 34 01146 05 Washer Lock M5 Spring 4 8 34 06358 00 Set Screw...

Page 66: ...1 Fuse 5 Amps Slow Blow Not Shown 2 5 76 66652 02 Fuse Holder In line 2 6 34 06243 00 Screw 8 32 x 0 75 TF Trilobe SST 2 7 66 U1 5321 2 Washer Plain 8 Type A 2 8 10 00431 03 Auxiliary Contactor 10 Amp...

Page 67: ...er SJ T 11364 2014 62 66122 03 Rev A Pb Hg Cd Cr VI PBB PBDE O O O O O O O O O O O O O O O O O O X O O O O O O O O O O O O O O O O O X O O O O O O O O O O O O O O O O O O O O O O O SJ T 11364 O GB T 2...

Page 68: ......

Page 69: ...2 10 4 34 06053 00 13 3 34 06099 22 12 2 34 06154 03 13 2 34 06243 00 15 1 34 06358 00 14 1 34 06386 00 12 2 34 60000 20 14 1 34 66627 00 10 2 10 4 34 66682 00 10 4 38 00631 00 10 2 10 4 38 00634 00...

Page 70: ...ubber 4 1 CO2 Sensor 3 1 6 1 6 5 CO2 Setpoint 4 2 4 3 Code 43 Cd43 4 1 4 4 Code 44 Cd44 4 3 Container Curtain 6 15 Container Preparation 6 13 Container Venting Procedure 4 4 E Evaporator Section 3 1 F...

Page 71: ......

Page 72: ...UTC Building Industrial Systems a business unit of United Technologies Corporation Stock symbol UTX Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse NY 13221 USA www carrier trans...

Reviews: